Page 7 - 16_DS187_E_0313_DC_Applications
P. 7

Safety lighting systems                         In safety lighting systems, loads are supplied with a.c.
                                                               voltage during normal operation and with battery-operated
                                                               d.c. voltage during emergency operation. Since surges may
                                                               occur during both operating states, DEHNsecure M 1 242
                                                               (FM) arresters are suited for direct and alternating currents.



                  DEHNsecure M 1 242 (FM)                          Technical data

                                                                   SPD classification according to EN 61643-11 type 1
                   Type              Part No.                      Max. continuous operating voltage (d.c.) U C  242 V
                   DSE M 1 242 (FM)  971 122 (971 127)             Lightning impulse current (10/350 µs) I imp  25 kA
                                                                   Voltage protection level U      < 2.5 kV
                                                                                     P
                                                                   Maximum direct current          2000 A
                                                                   For d.c. and a.c. operation     yes
                                                                   Max. continuous operating voltage (a.c.) U C  253 V
                                                                   Maximum backup fuse (a.c.)      10 A gL/gG




















                                           DEHNsecure

                                  AC/DC
                                                                          Lightning equipotential bonding,
                                                                          lightning current arrester / combined arrester
                                                                          Lightning Protection Zone




                                                                                                                    7