Page 8 - 9_DS145_E_0814_Rapid_LSA
P. 8

DEHNrapid  LSA Modules and approvals
                     ®
             Type                Part. No.      Max. continuous  Nominal current   SPD class  Approval

                                            operating voltage U
                                                           C
             DRL 10 B 180         907 400               180 V         0.4 A     G            VdS, GOST
             DRL 10 B 180 FSD     907 401               180 V         0.4 A     G            VdS, GOST
             DRL RE 5             907 420                5 V          0.4 A    O             VdS, GOST
             DRL RE 12            907 421               12 V          0.4 A    O             VdS, GOST
             DRL RE 24            907 422               24 V          0.4 A    O             VdS, GOST
             DRL RE 48            907 423               48 V          0,4 A    O             VdS, GOST
             DRL RE 60            907 424               60 V          0.4 A    O             VdS, GOST
             DRL RE 180           907 425               180 V         0.1 A    O             VdS, GOST
             DRL RD 5             907 440                5 V          0.4 A    O             VdS, GOST
             DRL RD 12            907 441               12 V          0.4 A    O             VdS, GOST
             DRL RD 24            907 442               24 V          0,4 A    O             VdS, GOST
             DRL RD 48            907 443               48 V          0.4 A    O             VdS, GOST
             DRL RD 60            907 444               60 V          0.4 A    O             VdS, GOST
             DRL RD 110           907 445               110 V         0.4 A    O             VdS, GOST
             DRL PD 180           907 430               180 V         0.1 A    O             VdS, GOST
             DRL HD 5             907 465                5 V          0.4 A    O               GOST
             DRL HD 24            907 470               24 V          0.4 A    O             VdS, GOST
             DPL 10 G3 110        907 214               110 V         0.4 A     B                –
             DPL 10 G3 110 FSD    907 216               110 V         0.4 A     B                –
                                                   VdS Vertrauen durch Sicherheit/Germany  GOST Gossudarstwenny Standart/Russia
             Characteristic               Symbol     Description
             Discharge capacity of an arrester    A  D1 impulse (10/350 µs), lightning impulse current ≥ 2.5 kA / core or ≥ 5 kA / total
             (according to the categories of EN/IEC   • Exceeds the discharge capacity of B – D
             61643-21)                               C2 impulse (8/20 µs), increased impulse load ≥ 2.5 kA / core or ≥ 5 kA / total
                                             B       • Exceeds the discharge capacity of C – D
                                                     C1 impulse (8/20 µs), impulse load ≥ 0.25 kA / core or ≥ 0.5 kA / total
                                             C       • Exceeds the discharge capacity of D
                                             D       Load < C
             Protective effect of an arrester    P1  Test level required for the terminal device: 1 or higher
             (limitation below the test levels accor-  P2  Test level required for the terminal device: 2 or higher
             ding to EN/IEC 61000-4-5)
                                              P3     Test level required for the terminal device: 3 or higher
                                              P4     Test level required for the terminal device: 4 or higher
             Energy coordination              k      Arrester has a decoupling impedance and is suitable for coordination with an
             (with another Yellow/Line arrester)     arrester marked with
                                                     Arrester is suitable for coordination with an arrester
                                                     with decoupling impedance k



                                                                                      immunity
                                                                                      test level according
                                                    lightning current   overvoltage   to EN/IEC 61000-4-5
                                                            G                 O
                                                                                            terminal
                                                                                            device
                                                                                                   1



                           energy coordination of Yellow/Line arresters   G O
                           depends on the cable length             discharge capacity


                                                           G                   O

                                                                                       specific protection of terminal
                                                     arrester can be coordinated   decoupling for coordination   devices according
                                                     with another arrester  (         )  with another arrester   (          )  to EN/IEC 61000-4-5



    8
   3   4   5   6   7   8   9   10   11   12