Page 7 - ATS022
P. 7

6





















          Technical Characteristics










                                                     ATS021                       ATS022
                                                                                  Not required
                     Auxiliary power supply          Not required                 (24-110 VDC is required only for Modbus
                                                                                  dialogue and 16 2/3 Hz systems)
                     Maximum voltage, Un             Max 480 VAC                  Max 480 VAC
                     Frequency, fn                   50, 60 Hz                    16 2/3, 50, 60, 400 Hz
          General                              H mm  96                           96
                     Dimensions                W mm  144                          144
                                               P mm  170                          170
                     Type of installation            Door mounting – DIN rail mounting  Door mounting – DIN rail mounting
                     Operating Mode                  Auto/Manual                  Auto/Manual
                     Normal and Emergency line       •                            •
                     monitoring
                     Normal and Emergency line CB    •                            •
                     control
                     Generator start-up              •                            •
                     Adjustable Generator shutdown
         Features    delay                           •                            •
                     Bus-tie                         -                            •
                     No-priority Line                -                            •
                     Priority Line Selection         -                            •
                     Display                         -                            •
                     Degree of protection            IP20                         IP20
          Environmental
          conditions  Operating temperature          -20 … +60°C                  -20 … +60°C
                     Maximum humidity                5% - 90% without condensation  5% - 90% without condensation
                     Min. voltage threshold          -30% … -5% Un                -30% … -5% Un
          Operating
          thresholds  Max. voltage threshold         +5% …+30% Un                 +5% …+30% Un
                     Frequency threshold             -10% … +10% fn               -10% … +10% fn
                     Test Mode                       •                            •
          Tests
                     Test Gen set Mode               •                            •
                     Electronic equipment
                     for use in power installations  EN-IEC 50178                 EN-IEC 50178
                                                     EN 50081-2                   EN 50081-2
          Compliance with  Electromagnetic compatibility  EN 50082-2              EN 50082-2
          standards
                                                     IEC 68-2-1                   IEC 68-2-1
                     Environmental conditions        IEC 68-2-2                   IEC 68-2-2
                                                     IEC 68-2-3                   IEC 68-2-3
   2   3   4   5   6   7   8