Page 208 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 208

3/132            ABB  MOTOR PROTECTION AND CONTROL

          —

          AF09..K ... AF38..K 3-pole contactors - with Push-in Spring terminals
          Electrical durability





          Electrical Durability for AC-1 Utilization Category - Ue ≤ 690 V.
   03
          Switching non-inductive or slightly inductive loads. The breaking current Ic for AC-1 is equal to the rated
          operational current of the load.
          Ambient temperature and maximum electrical switching frequency: see "Technical Data".



                     AF09  AF12  AF16  AF26  AF30, AF38
          Millions of operat-
          ing cycles
             10


              5

              3        9
                       7
                       5
                       3
              2    9   1
                   7
                   5
                   3
                   1
              1

             0.5

             0.3       9
                       7
                       5
                       3
             0.2       1
                                                13 57 9       15 9            13 57 9
                                                                                    13 57 9  15 9
                                       1  3  5  7  9                  1  3  5  7  9
             0.1
                2     3     5        10       20    30     50       100      200  300    500      1000
                                                  26.5                                          Breaking current Ic (A)


               Example:
               Ic / AC-1 = 26.5 A – Electrical durability required = 2 millions operating cycles.
               Using the AC-1 curves above select the AF26 contactor at intersection " " (26.5 A / 2 millions operating cycles).
   203   204   205   206   207   208   209   210   211   212   213