Page 752 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 752

6/14             ABB  MOTOR PROTECTION AND CONTROL

          —
          TF42 thermal overload relays – 0.10 to 38.0 A

          Technical data




          Main circuit – Utilization characteristics according to IEC/EN
          Type                              TF42
          Standards                         IEC/EN 60947–4–1, IEC/EN 60947-5-1, IEC/EN 60947-1
          Rated operational voltage Ue      690 V AC, 600 V DC
          Rated frequency                   DC, 50/60 Hz, 400 Hz
          Trip class                        10
          Number of poles                   3
          Duty time                         100%
          Operating frequency without early tripping  Up to 15 operations/h, see "Technical diagram – Intermittent periodic duty"
          Rated impulse withstand voltage Uimp  6 kV
          Rated insulation voltage Ui       690 V AC
          Auxiliary circuit according to IEC/EN
          Type                              TF42
          Rated operational voltage Ue      600 V
          Conventional free air thermal current Ith  N.C., 95-96 6 A
                                     N.O., 97-98 4 A
          Rated frequency                   DC, 50/60 Hz
          Number of poles                   1 N.O. + 1 N.C.
   06
          Ie / Rated operational current AC-15
          acc. to IEC/EN 60947-5-1 for utilization category
            110-120 V                N.C., 95-96 3.00 A
                                     N.O., 97-98 0.50 A
            220-230-240 V            N.C., 95-96 3.00 A
                                     N.O., 97-98 0.50 A
            440 V                    N.C., 95-96 0.75 A
                                     N.O., 97-98 0.50 A
            480-500 V                N.C., 95-96 0.75 A
                                     N.O., 97-98 0.50 A
          Ie / Rated operational current DC-13
          acc. to IEC/EN 60947-5-1 for utilization category
            24 V                     N.C., 95-96 1.25 A
                                     N.O., 97-98 1.25 A
            110-120-125 V            N.C., 95-96 0.55 A
                                     N.O., 97-98 0.55 A
            250 V                    N.C., 95-96 0.27 A
                                     N.O., 97-98 0.27 A
          Minimum switching capacity        17 V / 3 mA
          Short-circuit protective device  N.C., 95-96 6 A, fuse type gG
                                     N.O., 97-98 4 A, fuse type gG
          Rated impulse withstand voltage Uimp  6 kV
          Rated insulation voltage Ui       690 V
          Technical diagram – Intermittent periodic duty
           (Op/h)
           140
           120
           100        a
          switching frequency  60  t   = 1.5 s
           80
                      t   = 0.5 s
                   a
                   t   = 1 s
                 a
           40
               a
           20  t   = 3 s
               a
               t   = 5 s
            0                  2CDC232004F0214
             0  20  40  60  80  100  (%)
                  duty ratio
          ta: Motor starting time
   747   748   749   750   751   752   753   754   755   756   757