Miniature circuit-breakers
Selection table
S 200 S 200 M S 200 M S 200 P S 200 MR S 200 S SU 200 M SU 200 MR S 200 UDC SN 201 L SN 201 SN 201 M S200 80-100A
Series UC
Characteristics
B,C,D, B,C,D, B,C,D, B,C,D, B,C,D,
K,Z K,Z B,C, K, Z K,Z K,Z K,Z K B,C C,Z K C,Z K K K,Z B,C B,C,D B,C B,C
Rated current [A]
0.5 ≤ 0.5 ≤ 0.2 ≤ 0.2 ≤ 32 ≤ 50 ≤ 0.2 ≤ 6 ≤ 0.2 ≤ 0.2 ≤ 50 ≤ 40 ≤ 0.2 ≤ 1 ≤ 2 ≤ 2 ≤ 2 ≤ 80 ≤
In In In In In In In In In In In In In In In In In In
≤ 63 ≤ 63 ≤ 63 ≤ 25 ≤ 40 ≤ 63 ≤ 63 ≤ 20 ≤ 40 ≤ 35 ≤ 63 ≤ 63 ≤ 63 ≤ 63 ≤ 40 ≤ 40 ≤ 40 ≤ 100
Breaking [kA]
capacity
Reference Nr. Ue[V]
standard poles
IEC/EN 60898 Icn 230/400 6 10 10 25 15 15 6 4.5 6 10 6
IEC/EN Icu 1, 133 20 25 40 25 25 10 15 20 20
60947-2 1P+N 230 10 15 25 15 15 15 15 15 15 15 15 6 10 10 6
Alternating 253
current
2, 3, 4 230 20 25 10 *17 /6 *18 40 25 25 20
400 10 15 25 15 15 15 15 15 15 15 15 6
440 10 15 10 *17 /6 *18
2, 3, 4 500
690
Ics 1, 133 15 18.7 *8 20 18.7 18.7 6 10 10 10
1P+N 230 7.5 11.2 *8 12.5 11.2 7.5 11.25 11.25 7.5 7.5 4.5 6 7.5 6
253 7.5 *18 7.5 *18
7.5 *17 /6 *18
11.2 *17 11.2 *17
2, 3, 4 230 15 18.7 *8 20 18.7 18.7 10
400 7.5 11.2 *8 12.5 11.2 7.5 11.25 11.25 7.5 7.5 6
440 7.5 *18 7.5 *18
7.5 11.2 *8 7.5 *17 /6 *18
11.2 *17 11.2 *17
2, 3, 4 500
690
IEC/EN Icu 1, 24 20
60947-2 1P+N 60 10 10 15 10 10 15 15 10 10 10 15 15
Direct current 125
T=I/R≤5ms
for 220 10
all series, 250
except S280 2 48 20
UC and 125 10 10 15 10 10 15 15 10 10 10 15 15
S800S-UC, 250
where
T=I/R<15ms 440 10
500
800
3,4 375
500
750
1200