2/36             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
  2
          RCCBs
          F 200 series - B technical features




                                                       F200 B Type                          F200 B Type high ratings
                                                       F202 B 16-63 A      F204 B 25-63 A   F204 B 80-125 A
                    Standards                          IEC/EN 61008-1 EN 62423
          Electrical   Type (wave form of the earth leakage   B
          features  sensed)
                    Poles                              2P                  4P               4P
                    Rated current I  n            A    16, 25, 40, 63                       80, 125
                    Rated sensitivity I           A    0,03 - 0,3          0,03 - 0,3 - 0,5  0,03 - 0,3 - 0,5
                                Δn
                    Rated voltage U    IEC        V AC  230                230/400
                               e
                    Insulation voltage U i        V    500
                    Operating voltage of   IEC    V    110 - 253 V AC      110 - 254 V AC   110 - 254 V AC (80A)
                    circuit test Ut                    170 - 253 V AC (30 mA)  170 - 254 V AC (30 mA)  170 - 254 V AC (80A, 30mA)
                                                                                            200 - 440 V AC (125A)
                                                                                            250 - 440 V AC (125A, 30mA)
                    Min. operating voltage for detecting Type  V AC  0
                    A/AC residual currents
                    Min. operating voltage for detecting Type  V AC  50    50               50
                    B residual currents
                    Rated frequency               Hz   50/60                                50
                    Frequency range of residual current  kHz  B: 2                          B: 100
                    Rated conditional short-  SCPD - fuse   kA  10 (for 125 A fuse is gG 125 A)
                    circuit current Inc=I ∆  3  gG 100 A
                    Rated residual breaking capacity I =Im  kA  1                           125 A: 1,25
                                           ∆m
                    Rated impulse withstand voltage (1.2/50)  kV  4
                    Uimp
                    Dielectric test voltage at ind. freq. for 1   kV  2,5
                    min.
                    Overvoltage category               III, disconnector abilities
                    Surge current resistance (wave 8/20)  A  3.000         3.000 - 5.000 (B S)  3.000 - 5.000 (B S)
                    Maximum electronic consumption  W  1,2                 3,5              7,2
          Mechanical   Toggle                          Blue sealable in ON-OFF position
          features   Contact position indicator (CPI)  yes
                    Electrical life                    10.000                               2.000
                    Mechanical life                    20.000                               5.000
                    Protection degree  housing         IP4X
                                       terminals       IP2X
                    Environmental conditions (damp heat)   °C/RH  28 cycles with 55°C/90-96% and 25°C/95-100%
                    acc. to IEC/EN 60068-2-30
                    Ambient temperature   IEC     °C   -25…+60                              -25…+40
                    (with daily average ≤ +35
                    °C)
                    Storage temperature           °C   40…+70
          Installation  Terminal Type                  Failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected)
                                                       (cage for In > 63 A)  2
                    Min/Max Terminal size   IEC   Mm 2  1 - 25
                    top/bottom for cable
                    Terminal size top/bottom  IEC  Mm 2  10/10
                    for busbar
                    Tightening torque  IEC        Nm   2,8                                  3
                    Tool                               Flat tip PZ2
                    Mounting                           Any position on DIN rail EN 60715 (35 mm) by means of fast clip device
                    Supply                             Top/bottom
                    Withdrawal from busbar             It is possible without using any tools only from the   no
                                                       bottom
          Dimensions   Dimensions (H x D x W)  2P   Mm  85 x 69 x 35       85 x 69 x 70     85 x 69,5 x 72
          and weight  Weight           2P         g    200                 380              460
          Combination  Combinable with:
          with      auxiliary contact                  yes                                  no
          auxiliary
          elementsi  signal contact/auxiliary switch   yes
                    motor operating device             yes                                  no
                    shunt trip                         yes                                  no
                    undervoltage release               yes                                  no

          1  Ground-Fault Sensing and Relaying Equipment” (F200 up to 100 A)
          2  Prior to connection of aluminium conductors (≥ 4 mm 2 ) ensure that their contact points are cleaned, brushed and coated with grease
          3  for S700-E/K 100A, S750-E 63A, S750DR-E/K 63A and other SCPD coordination values are available.
   223   224   225   226   227   228   229   230   231   232   233