2/36 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
2
RCCBs
F 200 series - B technical features
F200 B Type F200 B Type high ratings
F202 B 16-63 A F204 B 25-63 A F204 B 80-125 A
Standards IEC/EN 61008-1 EN 62423
Electrical Type (wave form of the earth leakage B
features sensed)
Poles 2P 4P 4P
Rated current I n A 16, 25, 40, 63 80, 125
Rated sensitivity I A 0,03 - 0,3 0,03 - 0,3 - 0,5 0,03 - 0,3 - 0,5
Δn
Rated voltage U IEC V AC 230 230/400
e
Insulation voltage U i V 500
Operating voltage of IEC V 110 - 253 V AC 110 - 254 V AC 110 - 254 V AC (80A)
circuit test Ut 170 - 253 V AC (30 mA) 170 - 254 V AC (30 mA) 170 - 254 V AC (80A, 30mA)
200 - 440 V AC (125A)
250 - 440 V AC (125A, 30mA)
Min. operating voltage for detecting Type V AC 0
A/AC residual currents
Min. operating voltage for detecting Type V AC 50 50 50
B residual currents
Rated frequency Hz 50/60 50
Frequency range of residual current kHz B: 2 B: 100
Rated conditional short- SCPD - fuse kA 10 (for 125 A fuse is gG 125 A)
circuit current Inc=I ∆ 3 gG 100 A
Rated residual breaking capacity I =Im kA 1 125 A: 1,25
∆m
Rated impulse withstand voltage (1.2/50) kV 4
Uimp
Dielectric test voltage at ind. freq. for 1 kV 2,5
min.
Overvoltage category III, disconnector abilities
Surge current resistance (wave 8/20) A 3.000 3.000 - 5.000 (B S) 3.000 - 5.000 (B S)
Maximum electronic consumption W 1,2 3,5 7,2
Mechanical Toggle Blue sealable in ON-OFF position
features Contact position indicator (CPI) yes
Electrical life 10.000 2.000
Mechanical life 20.000 5.000
Protection degree housing IP4X
terminals IP2X
Environmental conditions (damp heat) °C/RH 28 cycles with 55°C/90-96% and 25°C/95-100%
acc. to IEC/EN 60068-2-30
Ambient temperature IEC °C -25…+60 -25…+40
(with daily average ≤ +35
°C)
Storage temperature °C 40…+70
Installation Terminal Type Failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected)
(cage for In > 63 A) 2
Min/Max Terminal size IEC Mm 2 1 - 25
top/bottom for cable
Terminal size top/bottom IEC Mm 2 10/10
for busbar
Tightening torque IEC Nm 2,8 3
Tool Flat tip PZ2
Mounting Any position on DIN rail EN 60715 (35 mm) by means of fast clip device
Supply Top/bottom
Withdrawal from busbar It is possible without using any tools only from the no
bottom
Dimensions Dimensions (H x D x W) 2P Mm 85 x 69 x 35 85 x 69 x 70 85 x 69,5 x 72
and weight Weight 2P g 200 380 460
Combination Combinable with:
with auxiliary contact yes no
auxiliary
elementsi signal contact/auxiliary switch yes
motor operating device yes no
shunt trip yes no
undervoltage release yes no
1 Ground-Fault Sensing and Relaying Equipment” (F200 up to 100 A)
2 Prior to connection of aluminium conductors (≥ 4 mm 2 ) ensure that their contact points are cleaned, brushed and coated with grease
3 for S700-E/K 100A, S750-E 63A, S750DR-E/K 63A and other SCPD coordination values are available.