          RCD-blocks
          DDA 800 technical features




                                                                                                                                 DDA 800 AC                DDA 800 A                  DDA 800 A AP-R            DDA 800 A S
                                              Standards                                                                          IEC/EN 60947-2 Ann. B
                                    Electrical   Type (wave form of the earth leakage sensed)                                    AC                        A                          A                         A
                                    features  Poles                                                                              2P, 3P, 4P
                                              Rated current In                                          A                        63                        63            100          63-100                    63          100
                                              Rated sensitivity IDn                                     A                        0.03-0.3                  0.03-0.3-0.5  0.3-0.5      0.03                      0.3-1       0.3-0.5*-1
         DDA 800
                                              Rated voltage Ue                                          V                        230/400 - 240/415 - 400/690
                                              Insulation voltage Ui                                     V                        690
                                              Operating voltage of circuit test Ut                      V                        195-690
                                              Rated frequency                                           Hz                       50...60
                                              Rated breaking capacity (Icn) acc. to IEC /EN 60947-2     A                        according to the breaking capacity of the associated MCB
                                              Rated residual breaking capacity  IDm  with S 800 C       kA                       according to the Icu of the associated MCB
                                                                               with S 800 N             kA                       according to the Icu of the associated MCB
                                                                               with S 800 S             kA                       according to the Icu of the associated MCB
                                              Rated impulse withstand voltage (1.2/50) Uimp             kV                       6
                                              Dielectric test voltage at ind. freq. for 1 min.          kV                       2.5
                                              Surge current resistance (wave 8/20)                      A                        NA                                                   3000                      5000
                                    Mechanical   Toggle                                                                          blue operating just from OFF position
                                    features  Electrical life                                                                    10000
                                              Mechanical life                                                                    20000
                                              Protection degree                housing                                           IP4X
                                                                               terminals                                         IP2X
                                              Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30  °C/RH              28 cycles with 55°C/90-96% and 25°C/95-100%
                                              Ambient temperature (with daily average ≤ +35 °C)         °C                       -25...+60
                                              Storage temperature                                       °C                       -40...+70
                                              Terminal size for cables         flexible                 mm  2                    6...50
                                                                               rigid                    mm  2                    6...70
                                              Tightening torque                                         Nm                       min. 3 / max. 4
                                              Mounting                                                                           on DIN rail EN 60715 (35 mm) by means of rapid fixing device
                                    Dimensions   Dimensions (H x D x  W)       2P                       mm                       108.2 x 82.3 x 81
                                    and weight                                 3P                       mm                       108.2 x 82.3 x 117
                                                                               4P                       mm                       108.2 x 82.3 x 117
                                              Weight                           2P                       g                        300 for 63 A - 415 for 100 A
                                                                               3P                       g                        400 for 63 A - 640 for 100 A
                                                                               4P                       g                        460 for 63 A - 765 for 100 A
                                    Combination  Combinable with:              S 800 N                                           yes
                                    with MCBs
                                                                               S 800 S                                           yes
                                    * only on 3P and 4P versions