Page 279 - Din prodcuts 2020
P. 279

2/87




          —                                                                                                            2
          RCBOs
          DS202C technical features




                                                                                                     DS202C
                                                                   DS202C     DS202C M   DS202C M
                                                                                                     M 110V
                    Standards                                                                        IEC 61009-1;
                                                                   IEC/EN 61009-1; IEC/EN 61009-2-1
                                                                                                     IEC 61009-2-1
          Electrical  Type (wave form of the earth leakage sensed)  A         A          APR         A
          features  Poles                                          2P         2P         2P          2P
                    Rated current In                         A     6 ≤ In ≤ 32  6 ≤ In ≤ 32  6 ≤ In ≤ 32  6 ≤ In ≤ 32
                    Rated sensitivity IDn                    A     0.03-0.3   0.01-0.03-0.3  0.03-0.3  0.03
                    Rated voltage Ue                         V     230-240    230-240    230-240     230-240
                    Insulation voltage Ui                    V     500        500        500         500
                    Operating voltage of circuit test Ut     V     110 (170 for    110 (170 for    110 (170 for    110-254
                                                                   30 mA) - 254  30 mA) - 254  30 mA) - 254
                    Rated frequency                          Hz    50…60      50…60      50…60       50…60
                    Rated breaking capacity acc. to   ultimate Icn  A  6000   10000      10000       10000
                    IEC/EN 61009
                    Rated breaking capacity acc. to   ultimate Icu  kA  10    10         10          10
                    IEC/EN 60947-2
                    2P @230 VAC             service Ics      kA    6          7.5        7.5         7.5
                    Rated residual breaking capacity IDm     kA    6          6          6           6
                    Rated impulse withstand voltage (1.2/50) Uimp  kV  4      4          4           4
                    Dielectric test voltage at ind. freq. for 1 min.  kV  2.5  2.5       2.5         2.5

                    Thermomagnetic release  B: 3 In ≤ Im ≤ 5 In    n          n          n
                    characteristic
                                            C: 5 In ≤ Im ≤ 10 In   n          n          n           n
                    Surge current resistance (wave 8/20)     A     NA for A, AC versions; 3000 for APR version
          Mechanical   Toggle                                      black sealable in ON-OFF position
          features  Flag indicators                                differential trip indicator (blue)

                                                                   contact position indicator (green/red)
                    Electrical life                                10000      10000      10000       10000
                    Mechanical life                                20000      20000      20000       20000
                    Protection degree       housing                IP4X       IP4X       IP4X        IP4X
                                            terminals              IP2X       IP2X       IP2X        IP2X
                    Environmental conditions (damp heat)     °C/RH 28 cycles with 55°C/90-96% and 25°C/95-100%
                    acc. to IEC/EN 60068-2-30
                    Reference temperature for setting of thermal element  °C  30  30     30          30
                    Ambient temperature (with daily average ≤ +35 °C)  °C  -25…+55  -25…+55  -25…+55  -25…+55
                    Storage temperature                      °C    -40…+70    -40…+70    -40…+70     -40…+70
          Installation  Terminal type       top                    failsafe bi-directional cylinder-lift terminal at top and bottom
                                                                   (shock protected)
                                            bottom                 failsafe bi-directional cylinder-lift terminal at top and bottom
                                                                   (shock protected)
                    Terminal size top/bottom for cables      mm 2  25/25      25/25      25/25       25/25
                    Terminal size top/bottom for busabar     mm 2  10/10      10/10      10/10       10/10
                    Tightening torque top/bottom             Nm    2.8        2.8        2.8         2.8
                    Mounting                                       on DIN rail EN 60715 (35 mm) by means of fast clip  device
                    Mounting position                              Any        Any        Any         Any
                    Connection                                     from top and   from top and   from top and   from top and
                                                                   bottom     bottom     bottom      bottom
          Dimensions   Dimensions (H  x D x W)               mm    85 x 69 x 35  85 x 69 x 35  85 x 69 x 35  85 x 69 x 35
          and weight  Weight                                 g     239        239        239         239
          Combination  Combinable with:     auxiliary contact      yes        yes        yes         yes
          with                              signal contact         yes        yes        yes         yes
          auxiliary
          elements                          shunt trip             yes        yes        yes         yes
                                            undervoltage release   yes        yes        yes         yes
   274   275   276   277   278   279   280   281   282   283   284