Page 290 - Din prodcuts 2020
P. 290

2/98             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
  2
          RCBOs
          DS203NC technical features




                                                           DS203NC L                  DS203NC
          Standards                                        IEC/EN 61009-1; IEC/EN 61009-2-1  IEC/EN 61009-1; IEC/EN 61009-2-1
          Electrical features
          Type (wave form of the earth                     AC, A, APR                 AC, A, APR, S
          leakage sensed)
          Number of poles                                  3P+N                       3P+N
          Rated current In                        A        6≤ In ≤ 32A                6≤ In ≤ 32A
          Rated sensitivity IDn                   mA       30-300                     30-100-300
          Rated voltage Ue                        V        400-415V                   400-415V
          Insulation voltage Ui                   V        500 V AC                   500 V AC
          Overvoltage category                             III                        III
          Pollution degree                                 2                          2
          Operating voltage of circuit test Ut    V        195 (300 for 30 mA) - 440
          Rated frequency                         Hz       50/60                      50/60
          Rated breaking          ultimate Icn    A        4500                       6000
          capacity acc. to IEC/ EN 61009
          Rated breaking          ultimate Icu    kA       6                          10
          capacity acc. to IEC/EN 60947-2
                                  service Ics     kA       4.5                        5
          Rated residual breaking                 kA       4.5                        6
          capacity IDm acc. To EN 61009
          Rated residual breaking                 kA       4.5                        4.5
          capacity IDm acc. to IEC 61009
          Rated impulse withstand voltage         kV       4                          4
          (1.2/50) Uimp
          Dielectric test voltage at ind. freq.   kV       2.5                        2.5
          for 1 min.
          Thermomagnetic release -   B: 3 In ≤ Im ≤ 5 In                              n
          characteristic
                                  C: 5 In ≤ Im ≤ 10 In     n                          n
                                  K: 10 In ≤ Im ≤ 14 In                               n
          Surge current resistance (wave 8/20)    A        NA for A, AC versions; 3000 for APR   NA for A, AC versions; 3000 for APR
                                                           version                    version; 5000 for S version
          Mechanical features
          Housing                                          Insulation group II, RAL 7035  Insulation group II, RAL 7035
          Toggle                                           black, sealable in ON-OFF positions  black, sealable in ON-OFF positions
          Flag indicator                                   Differential trip indicator:   Differential trip indicator:
                                                           blue on toggle             blue on toggle
          Contact position indication                      CPI on window              CPI on window
          Electrical life                         operations 10000                    10000
          Mechanical life                         operations 20000                    20000
          Protection degree       housing                  IP4X                       IP4X
                                  terminals                IP2X                       IP2X
          Shock resistance acc. to IEC/EN                  30g - 2 shocks - 13ms      30g - 2 shocks - 13ms
          60068-2-27
          Vibration resistance acc. to IEC/                0,35mm or 5g - 20 cycles at   0,35mm or 5g - 20 cycles at
          EN 60068-2-6                                     5…150…5 Hz without load    5…150…5 Hz without load
          Environmental conditions (damp heat) acc. to IEC/EN   °C/RH  28 cycles with 55°C/90-96% and   28 cycles with 55°C/90-96% and
          60068-2-30                                       25°C/95-100%               25°C/95-100%
          Reference temperature for setting of thermal element  °C  30                30
          Ambient temperature (with daily average ≤ +35 °C)  °C  -25…+55              -25…+55
          Storage temperature                     °C       -40…+70                    -40…+70
   285   286   287   288   289   290   291   292   293   294   295