Page 437 - Din prodcuts 2020
P. 437
4/83
—
Auxiliary elements for S800
S800 Busbar system
4
S800 Busbar system
The S800 busbar system is comprised of:
S804-BBPC120 120 mm feed block, 4-pole
2
S804-BB250 250 A busbar, 4-pole and neutral with 24 contacts pins
S804-BB6 250 A busbar, 4-pole with 6 contacts pins
S803-BB250 250 A busbar, 3-pole with 24 terminal lugs and 2 end caps
S803-BBPC120 120 mm feed block, 3-pole
2
S800-BBIC Optional contact-protection cap for exposed terminal lugs
S800-END Optional end cap
The busbar, which can be shortened in length by the user, ensures the safe and rational
2
connection of the S800 high performance MCB. A cable cross-section of up to 120 mm
can be connected at the feed block.
Busbar S803-BB250/S804-BB250
Max. rated current I n
Side feed A 125
Middle feed A 250
Conditional rated short-circuit current kA eff 100 with T max connected upstream
Poles 3/4
Rated operational voltage U
e
(AC) 50/60 Hz V 400/690
Rated insulation voltage U i V 690
Rated impulse withstand voltage U kV 8
imp
Rated frequency Hz 50
Standard EN/IEC 60439-2
Material of rails E-C 58 half-standard, rolled F25
u
Material of insulation profile Material group I; UL94 V-0
Material of end caps Material group I; UL94 V-0
Free of halogen and phosphate
Busbar cross sections mm 2 60
Overvoltage category III
Pollution degree 2
Feed block S803-BBPC120/S804-BBPC120
Max. rated current I n A 250
Poles 3/4
Rated operational voltage U V 400/690
e
Rated frequency Hz 50
Standard EN/IEC 60439-2
Material of terminals Material group I
Housing material Material group I; UL94 V-0, Free of halogen
and phosphate
Tightening torque -
on feed side Nm 19
on busbar side Nm 3
Connection cross-section mm 2 1.6…120
Pollution degree 2