Page 484 - Din prodcuts 2020
P. 484

5/40             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          OVR Type 2 pluggable QuickSafe® surge protective devices
          TNC 230 V networks


          Technical features
          Types                                OVR T2 3L 40-   OVR T2 3L 40-   OVR T2 3L 80-    OVR T2 3L 40-
                                               275 P QS        275s P QS       275s P QS        350 P QS
  5
          with auxiliary contact (TS)          OVR T2 3L 40-   OVR T2 3L 40-   OVR T2 3L 80-    OVR T2 3L 40-
                                               275 P TS QS     275s P TS QS    275s P TS QS     350 P TS QS
          Technology                           Varistor        Varistor        Varistor         Varistor
          Electrical features
          Standard                             IEC 61643-11/EN   IEC 61643-11/EN   IEC 61643-11/EN   IEC 61643-11/EN
                                               61643-11        61643-11        61643-11         61643-11
          Type/test class                      T2/II           T2/II           T2/II            T2/II
          Protected lines                      3               3               3                3
          System network                       TNC             TNC             TNC              TNC
          Type of current                      AC 47-63 Hz     AC 47-63 Hz     AC 47-63 Hz      AC 47-63 Hz
          Voltage regulation of the system network  ± 20 %     ± 20 %          ± 20 %           ± 50 %
          Nominal system voltage Un (L-PEN/L-L)  [V]  230/400  230/400         230/400          230/400
          Max. cont. operating voltage Uc  [V]  275            275             275              350
          Nominal dc voltage Un dc L-PE/Un dc L-L  [V dc]  320/640  -          -                375/750
          Max. dc. cont. operating voltage Ucdc   [V dc]  355/710  -           -                415/830
          L-PE/Ucdc L-L
          Maximum discharge current Imax (8/20)  [kA]  40      40              80               40
          Maximum impulse current Iimp (10/350)  [kA]  2       2               6.25             2
          Nominal discharge current In (8/20)  [kA]  20        20              20               20
          Voltage protection level Up at In (L-PE)  [kV]  1.25  1.4            1.4              1.5
          Voltage protection level Ures at 3kA  [kV]  0.8      0.5             0.5              1.0
          Voltage protection level Ures at 5kA  [kV]  0.85     0.7             0.7              1.05
          Voltage protection level Ures at 10kA  [kV]  1.0     0.9             0.9              1.2
          TOV (Temporary overvoltage) withstand Ut  [V]  337/-  337/-          337/-            455/-
          (L-N: 5s./N-PE: 200ms)
          Uoc                            [kV]  -               -               -                -
          Response time                  [ns]  ≤ 25            ≤ 25            ≤ 25             ≤ 25
          Short-circuit withstand capability Isccr  [kA]  100  100             100              100
          Backup      fuse (gG)          [A]   ≤ 125           ≤ 160           ≤ 160            ≤ 125
          protection   circuit breaker   [A]   ≤ 125           ≤ 125           ≤ 125            ≤ 125
          maximum     (B or C curve)
          rating
          Pluggable cartridge                  Yes             Yes             Yes              Yes
          Integrated QuickSafe® technology     Yes             Yes             Yes              Yes
          State indicator                      Yes             Yes             Yes              Yes
          Safety reserve                       No              Yes             Yes              No
          Auxiliary contact                    Yes (TS option)  Yes (TS option)  Yes (TS option)  Yes (TS option)
          Installation
          Wire range   solid wire        [mm²]  2.5 … 35       2.5 … 35        2.5 … 35         2.5 … 35
          (L, N, PE)
                      stranded wire      [mm²]  2.5 … 25       2.5 … 25        2.5 … 25         2.5 … 25
          Stripping length (L, N, PE)    [mm]  12.5            12.5            12.5             12.5
          Tightening torque (L, N, PE)   [Nm]  2.8             2.8             2.8              2.8
          Auxiliary contact (TS)
          Contacts information                 1 NO - 1 NC     1 NO - 1 NC     1 NO - 1 NC      1 NO - 1 NC
          Min. load                            12 DC - 10 mA   12 DC - 10 mA   12 DC - 10 mA    12 DC - 10 mA
          Max. load                            250 V AC - 1A   250 V AC - 1A   250 V AC - 1A    250 V AC - 1A
          Connection cross-section       [mm²]  1.5            1.5             1.5              1.5
          Miscellanous characteristics
          Stocking and operating temperature  [°C]  -40 to +80  -40 to +80     -40 to +80       -40 to +80
          Maximal Altitude                 [m]  5000           5000            5000             5000
          Degree of protection                 IP 20           IP 20           IP 20            IP 20
          Fire resistance according to UL 94   V0              V-0             V-0              V0
   479   480   481   482   483   484   485   486   487   488   489