Page 626 - Din prodcuts 2020
P. 626

5/182            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          SELVTESTER insulation monitoring devices for insulated networks at 24 V AC/DC




                                    Technical features
                                    Network voltage and auxiliary   24 V 50-60 Hz/DC ± 20 %
                                    power supply
  5
                                    Max power dissipation     3 VA – 3 W
                                    Measurement current       max. 0.5 mA
                                    Internal impedance        50 kohm
                                    Threshold                 programmable to 10 ÷ 50 kohm (4 levels using microswitches)
                                    Activation delay          about 1 second
          SELVTESTER
                                    Signals                   led ON, led ALARM +, led ALARM -
                                    Output                    for up to 2 QSD-230/24-C, max. 24 V 1 A remote panels
                                    Operating temperature     -10 ÷ 60 °C
                                    Storage temperature       -20 ÷ 70 °C
          H+Line                    Relative humidity         ≤ 95 %
                                    Insulation
                                                              2.5 kV 60 sec./4 kV imp. 1.2/50µs
                                    Terminal cross-section    4 mm 2
                                    Protection degree         IP20, IP40 when the cover is closed
                                    Modules                   3
                                    Weight                    200 g
                                    Reference standards       IEC 60364-7-710, EN 61326-1, EN 61010-1

                                    SELVTESTER for insulated networks at 24 V AC/DC
                                    It is used to monitor permanently the insulation of safety extremely low voltage circuits
                                    (up to 24 V) especially scialitic lamps.


                                    Function             Bbn     Order details                 Price  Weight  Pack
                                                         8012542                               1    1 piece  unit
                                                                                               piece
                                                         EAN     Type code      Order code          kg     pc.
                                    Insulation monitoring  884705  SELVTESTER-24  2CSM211000R1511   0.250  1
   621   622   623   624   625   626   627   628   629   630   631