6/14             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Command and signaling
          E 200 switches




                                    Technical data E200 80…125 A
                                    Electrical Data
                                    Standards                        DIN EN 60947-3 (VDE0660-107); IEC/EN 60947-3
                                    Number of poles                  1P, 2P, 3P, 4P
                                    Rated current I                  80...125 A
                                              e
                                    Rated voltage U   e              240/415 V AC; 60 V DC
  6
                                    Rated frequency f                50/60 Hz; DC
                                    Utilization category             I  80 … 125 A    AC-22A (1..4-pole)
                                                                      e
          E 200                                                                       DC-21B  (1/2-pole)
                                                                     Acc. to  DIN EN 60947-3 (VDE0660-107); IEC/EN 60947-3
                                    Protection fuse                  NH 00 gG ≤ Rated current E200
                                    Positive opening                 Acc. to DIN VDE 0113
                                    Rated conditional short-circuit current  80 … 100 A (1- to 4-pole): 25 kA, 125 A (1- to 4-pole): 6 kA
                                    Surge withstand capability U     4 kV (EN 60947-1)
                                                        imp
                                    Min. voltage U                   12 V AC/DC bei 0.1 VA
                                              min.
                                    Min. contact loading             24 V AC; 4 mA
                                    Mechanical Data
                                    Housing                          Grey, RAL 7035
                                    Toggle                           Red (RAL 3000) / grey (RAL 7000), sealable
                                    Contact position indication      On toggle (I ON / 0 OFF), on dome (I / 0)
                                    Protection degree acc. to IEC/EN 60529  IP10, IP40 in enclosure with cover
                                    Electrical endurance             80 … 100 A: 1,500 ops., 125 A: 1,000 ops.
                                    Mechanical endurance             20,000 ops.
                                    Environmental conditions acc. to IEC/EN   Constant climate 23/83, 40/93, 55/20 [°C/RH]
                                    60068-2-30
                                                                     Alternating climate 25/95 - 40/93 [°C/RH]
                                    Ambient temperature              -25 … +55 °C
                                    Storage temperature              -40 … +70 °C
                                    Installation
                                    Terminal size                    2.5 to 50 mm   2
                                    Cross-section busbar             ≥ 16 mm 2
                                    Tigthening torque                2.5 Nm
                                    Screw driver                     Nr. 2 Pozidriv
                                    Mounting                         On DIN rail 35 mm acc. to EN 60715 by fast clip
                                    Mounting position                Any
                                    Supply                           Any
                                    Dimensions and weight
                                    Mounting dimensions acc. to DIN 43880  Mounting dimension 1
                                    Pole dimensions (H x D x W)      85 x 70 x 17.5 mm
                                    Pole weight                      Ca. 95 g
                                    Accessories
                                    Auxiliary contact                Max. 3x S2C-H 6R
                                    Approvals                        CE and RoHS conform
                                                                     Approvals: VDE, CCC, KEMA, EAC