Page 745 - Din prodcuts 2020
P. 745

8/5




          —
          Energy efficiency

          Network analyzers – M4M 20 and M4M 30



          Technical features
          Type                                                     M4M 20 - Class 0,5S            M4M 30 - Class 0,5S










          Communication protocol
                                                   M4M 20 Modbus, M4M 20 I/O, M4M 20   M4M 30 Modbus, M4M 30 I/O, M4M 30
          Modbus RTU
                                                             Rogowski                       Rogowski
                                                                                                                       8
          Communication interface                                      RS485 with optical isolation
          Baud rate                                                   9.6, 19.2, 38.4, 57.6, 115.2 kbps
          Parity number                                                    Odd, Even, None
          Stop bit                                                             1, 2
          Address                                                             1-247
          Connector                                                        3 pole terminal
          Profibus DP-V0                                   M4M 20 Profibus                M4M 30 Profibus
          Protocol                                    Profibus with slave DP-V0 function in compliance with IEC 61158 regulations
          Communication interface                                      RS485 with optical isolation
          Baud rate                                               Automatic detection [9.6 kbps - 12 Mbps]
          Address                                                             0-126
          Connector                                      DB 9 female connector (do not use connectors with 90° cable outlet)
                                                                     Green for communication status
          LED indicators
                                                                      Red for communication error
          Modbus TCP/IP                                    M4M 20 Ethernet               M4M 30 Ethernet
          Protocol                                                         Modbus TCP/IP
          Communication interface                              RJ45                  RJ45 (2 ports for daisy-chain)
          BACnet                                           M4M 20 Bacnet                  M4M 30 Bacnet
          Protocol                                                           BACnet/IP
          Communication interface                                             RJ45

          Bluetooth
          Type                                                         BLE (Bluetooth Low Energy)

          Real-time clock
          Clock drift                                           -                       ~ 0.4 seconds per day
          Battery backup time                                   -                     ~ 3 days without aux supply

          Standards
          Power metering and monitoring devices (PMD)             IEC 61557-12 (IEC 62053-22, IEC 62053-23)
          Electrical safety                                                 IEC 61010-1
                                                  IEC 61326-1 (IEC 61000-3-2, IEC 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-
          EMC
                                                          4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11)
   740   741   742   743   744   745   746   747   748   749   750