          Energy efficiency
          Front-panel analogue instruments




                                    Technical features
                                    Rated max. reference voltage for  [V]  600 (a.c meters), 300 (d.c. meters)
                                    insulation
                                    Test voltage            [V]        2000 eff. (50 Hz/1 min)
                                    Accuracy class                     1.5 (0.5 for frequency meters)
                                    Overload capacity a
                                    - ammetric windings                up to In x 10/< sec. up to In x 2/permanent
                                    - voltmetric windings              up to Un x 2/< 5 sec. up to Un x 1.2/permanent
          Front panel analogue instruments
                                    Operating temperature   [°C]       -10...+55
                                    Storage temperature     [°C]       -40...+70
                                    Average and max. relative          65% (yearly average)
                                    humidity (DIN 40040) b             85% (+35 °C/60 days a year)
                                    Vibration resistance (IEC 50-1)  [g (9.81 m/s)]  0.08-1.8 (0.35 mm/10-55 Hz; 3 axis/6 h)
  8
                                    Degree of protection               IP52 indoors
                                                                       IP00 on the terminals (IEC 144. DIN 40050)
                                                                       IP20 with suitable terminal covers
                                    Materials
                                    - cases and front edge             self-extinguishing thermosetting material
                                                                       in accordance with UL94 V-0, fungus and termite
                                                                       resistant
                                    - pointers (DIN 43802) c           molded aluminium
                                    - terminals                        brass
                                    Assembly                           vertical/horizontal with special screw-on brackets d
                                    Dimensions W x H x D    [mm]       48 x 48 X 53 72 x 72 x 53 96 x 96 X 53
                                    (DIN 43700/43718)
                                    Applicable standards               IEC EN 61010-1

                                    a  The overload can be greater for instruments enabled by a CT because the transformer generally keeps secondary current
                                     peaks to within 10 In.
                                    b  Tropicalization enables the instruments to withstand up to 95% max. relative humidity (+35 °C/60 days). In accordance
                                     with DIN standard 40040, they must be protected against any penetration of humidity inside the device. Terminals,
                                     screws, washers, bolts and magnets are galvanically protected against rust, while the electrical circuits are painted with
                                     the special Multicolor PC52 varnish.
                                    c The pointer damping time is 1 second. The recorded values are cleared by pressing the control provided.
                                    d  With 0.5 mm -19 mm thick panels, the screws must be attached in the fixing position nearest to the front edge of the
                                     measuring device, whereas the 20 mm - 39 mm thick panels require the screws to be fixed in the position furthest away
                                     from the front edge.