Page 879 - Din prodcuts 2020
P. 879

9/49




          —
          SMISSLINE TP plug-in system
          Incoming terminal block and components – 125 A system




                                    General
                                    The incoming terminal block is used to connect cables directly to the busbars. The terminals
                                    act directly on the busbars and therefore fix the incoming terminal block. Removable
                                    terminal tops permit the connection of continous conductrors (risers) white horizontal
                                    or vertical cable entry is also possible.
                                    Instead of using the incoming terminal block, the power supply can also be realized via
                                    a  device (e.g. residual current operated circuit breaker, miniature circuit breaker or switch
                                      disconnector).

                                    Power supply left or right, maximum 125 A.








                                                                                                                       9






                                    Power supply in centre, maximum 160 A.
                                    A maximum of 125 A is permitted on either side. A total of 160 A must not be exceeded.















                                    Incoming terminal blocks ZLS924
                                    A standard incoming terminal block whose cover provides protection against accidental
                                      contact. Construction height 50 mm. The base plate can be fitted with a maximum of 4
                                    main terminals L1, L2, L3 and N for the busbars, and 2 auxiliary termiinals LA and LB for
                                    the  auxiliary busbars.
   874   875   876   877   878   879   880   881   882   883   884