Page 140 - Enclosed
P. 140

140              SAFETY SWITCHES AND ENCLOSED SWITCH-DISCONNECTORS SAFE AND DEPENDABLE PERFORMANCE




          —
          Ordering information
          Technical data for auxiliary contacts








         Performance data of auxiliary contacts according to IEC 60947-5-1
          For OA1G_, OA3G_                                                  For OA1G_, OA3G_
          AC15            DC12                    DC13                      U i /[V]    690
          Ue/[VAC]  I /[A]   U /[VDC]  I /[A]     P/[W]  I /[A]  P/[W]      U imp /[kV]  4
                   e       e      e               e
          230     6       24      10      240     2       50                Pollution degree  3
          400     4       72      4       290     0.8     60                I th /[A]   16
          415     4       125     2       250     0.55    70                Cable size  1...2 x 0.75...2.5 mm 2
          690     2       250     0.55    140     0.27    70                Maximum fuse  16A / gG
                          440     0.1     44                                NEMA        A600, R300, wire size: 18 - 14 AWG, 1(2)









          Function table of auxiliary contacts
          Handle position           Main contacts            Aux./Test contacts N.O.   Test indication contact N.O.
          Test                      Open                     Closed                    Closed
          0                         Open                     Open                      Open
          I                         Closed                   Closed                    Open











                                                                                            ON
          Handle indications and functions

          The handle indicates the position of the main contacts of the switch
          with complete reliability in all situations. If the contacts are welded           ON
          together, the handle does not reach the OFF-position but remains
          between ON and OFF, maintaining the door interlock and preventing   OFF        OFF
          padlocking.


          When operating the switch to the Test-position with a test handle, the
          test auxiliary contacts change position. The main contacts remain open.  Test
   135   136   137   138   139   140   141   142   143   144   145