Page 31 - Enclosed
P. 31

SAFET Y SWITCHES                                                                   31




          —
          Ordering information
          Steel sheet enclosed safety switches

                                                                                                                      02




                                  —
                                  Safety switches with C-flange cable entries, 3-pole, IP65, black handle

                                  The delivery includes a black pistol type handle (I-O/ON - OFF indication), PE-terminal,
                                  grey enclosure. Fixed cable entries with C-flange entries. Entry plate fixing profiles are
                                  used also for mounting the safety switch. Auxiliary contacts are wired to the terminal
                                  blocks in sizes 200A...800A. Cover interlock and defeatable interlock included.


                                  Cable entries from bottom
         OT160EVAUM3TZ,
         OT200KAUC3TZ             Max.
                                  motor
                                  output/                       Enclosure   Cover
                                  AC-23A   Cable openings      dimensions   flanges                       Weight
                                  415V            /side Height  Width  Depth  included                     /unit
                                  kW/A             mm    mm    mm    mm    [pcs]      Type     Order number  kg
                                  Additional knock-outs: 20.5mm, 25.5mm
                                  Auxiliary contacts included: 1NO+1NC • Auxiliary contacts max: 2NO+2NC
                                  45/90     Blank/2x63, 2x50,   400  400  230  1  OT90GAUM3TZ  1SCA161656R1001  14.5
                                  55/125           2x40  400   400   230      1  OT125GAUC3TZ  1SCA148440R1001  14.5
                                  Additional knock-outs: 20.5mm, 25.5mm
                                  Auxiliary contacts included: 2NO+1NC • Auxiliary contacts max: 2NO+1NC
                                  80/160                 600   400   230      1  OT160EVAUC3TZ  1SCA147978R1001  21.91
                                  110/200                600   400   230      1  OT200KAUC3TZ  1SCA022340R0930  23
                                            Blank/2x63, 2x50,
                                  132/200                800   400   230      1  OT250KAUC3TZ  1SCA022340R1310  27
                                  160/315          2x40  800   400   230      1  OT315KAUC3TZ  1SCA022340R1740  27
                                  220/400                800   400   230      1  OT400DAUC3TZ  1SCA022340R2120  30
                                  315/570   Blank/4x63, 4x50  1000  800  230  2  OT630KAUC3TZ  1SCA022340R2550  50

                                  Compression glands or flanges to be ordered separately.