Page 104 - Ferraz semiconductor DIN
P. 104

Semiconductor fuses
       Semiconductor (AC) fuses


       Protistor Square-body Fuses
                     ®
       PSC aR sizes 3x - 450V to 700 VAC
       Curves set






       Size 32



                                                                  Cut-off characteristics
                                                                Below, right: Curves indicating for each rated-
                                                                current the peak value I that the current may
                                                                                       c
                                                                reach as a function of the prospective fault
                                                                current Ip.

































                                                             Time-current characteristics
                Size
                 32                                        Above, left: Curves indicating pre-arcing time for
                                                           each rated current as a function of RMS value of
                                                           pre-arcing current I.
                                                           - Tolerances on this current ± 8 %.
                                                           - Beyond 30 sec or 10 sec, small overloads must be
                                                           eliminated by another device.
                                                           - Curve CC’ represents the maximum times taken by
                                                           the associated device to clear small overloads; only
                                                           its horizontal line is represented. Its oblique line must
                                                           be plotted according to sketch, top right corner.
                                                           - The intersection of the fuse and CC’ curves indicates
                                                           the minimum breaking current Ipm of the fuse.



                                                             Maximum values of total
                                                           operating I t and total operating
                                                                          2
                                                           times
                                                           Left: Horizontal curves indicating the maximum
                                                           values of total operating I t (I t ) as function of the
                                                                                        2
                                                                                    2
                                                                                         t
                                                           prospective current I at 660 V, cos ϕ = 0.15.
                                                                               p
                                                           The oblique lines indicate the corresponding total
                                                           operating time T , with pre-arcing time in brackets.
                                                                           t
                                                          SCAC87
       12/04
   99   100   101   102   103   104   105   106   107   108   109