Page 227 - Ferraz semiconductor DIN
P. 227

Semiconductor fuses
                                                   Semiconductor (AC) fuses


                                                                                ®
                                                                 Protistor Square-body Fuses
                                                  PSC aR sizes 7x - 650 V to 1300 VAC
                                                                                                 Curves set






                                                                                                     Size 2x72
             Cut-off characteristics
                                                                           Time-current characteristics
             Curves indicating for each rated
             current the peak value I that the current may
                                    c
             reach as a function of the prospective fault
             current I .
                     p



































             Time-current characteristics
             Curves indicating pre-arcing time for each rated current
             as a function of RMS value of pre-arcing current I.              Size
             - Tolerances on this current ± 8 %.                             2x73
             - Beyond 30 sec, small overloads must be eliminated by
              another device.
             - Curve CC’ represents the maximum times taken by the
              associated device to clear small overloads; only its
              horizontal line is represented. Its oblique line must be
              plotted according to  sketch, top right corner.
             - The intersection of the fuse and CC’ curves indicates
              the minimum breaking current I pm  of the fuse.





                                                               2
             Maximum values of total operating I t
             and total operating times
             Horizontal curves indicating the maximum values of
             total operating I t (I t ) as function of the prospective
                            2
                               2
                                t
             current I at 1000V or 850 V(*), cos ϕ = 0.15.
                    p
             The oblique lines indicate the corresponding total
             operating time T , with pre-arcing time in brackets.
                            t