Page 29 - Ferraz semiconductor DIN
P. 29
Semiconductor fuses
Semiconductor (AC) fuses
Protistor Square-body Fuses
®
PSC aR sizes 3x - 450V to 700 VAC
Curves set
Size 30
Cut-off characteristics
Below, right: Curves indicating for each rated-
current the peak value I that the current may
c
reach as a function of the prospective fault
3,2 mm
current Ip.
Time-current characteristics
Size
Above, left: Curves indicating pre-arcing time for
30
each rated current as a function of RMS value of
pre-arcing current I.
- Tolerances on this current ± 8 %.
- Beyond 30 sec or 10 sec, small overloads must be
eliminated by another device.
- Curve CC’ represents the maximum times taken by
the associated device to clear small overloads; only
its horizontal line is represented. Its oblique line must
be plotted according to sketch, top right corner.
- The intersection of the fuse and CC’ curves indicates
the minimum breaking current Ipm of the fuse.
Maximum values of total
operating I t and total operating
2
times
Left: Horizontal curves indicating the maximum
2 2
values of total operating I t (I t ) as function of the
t
prospective current I at 660 V, cos ϕ = 0.15.
p
The oblique lines indicate the corresponding total
operating time T , with pre-arcing time in brackets.
t
SCAC85
12/04