Page 49 - Ferraz semiconductor DIN
P. 49

Semiconductor fuses
                                                   Semiconductor (AC) fuses


                                                                 Protistor Square-body Fuses
                                                                                ®
                                                      PSC aR sizes 3x - 450V to 700 VAC
                                                                                                 Curves set






                                                                                                         Size 33

                                                                       Cut-off characteristics

                                                                     Below, right: Curves indicating for each rated
                                                                     current the peak value I that the current may
                                                                                             c
                                                                     reach as a function of the prospective fault
                                                                     current I .
                                                                              p
































                                                                  Time-current characteristics
                      Size                                      Above, left: Curves indicating pre-arcing time for
                       33
                                                                each rated current as a function of RMS value of pre-
                                                                arcing current I.
                                                                - Tolerances on this current ± 8 %.
                                                                - Beyond 30 sec or 10 sec, small overloads must be
                                                                eliminated by another device.
                                                                - Curve CC’ represents the maximum times taken by
                                                                the associated device to clear small overloads; only its
                                                                horizontal line is represented. Its oblique line must be
                                                                plotted according to sketch, top right corner.
                                                                - The intersection of the fuse and CC’ curves
                                                                indicates the minimum breaking current Ipm of the
                                                                fuse.


                                                                  Maximum values of total
                                                                               2
                                                                operating I t and total operating
                                                                times
                                                                Left:  Horizontal curves indicating the maximum
                                                                                           2
                                                                                        2
                                                                values of total operating I t (I t ) as function of the
                                                                                             t
                                                                prospective current I at 660 V, cos ϕ = 0.15.
                                                                                   p
                                                                The oblique lines indicate the corresponding total
                                                                operating time T , with pre-arcing time in brackets.
                                                                                t
                                                          SCAC88                                               12/04
   44   45   46   47   48   49   50   51   52   53   54