Page 35 - Ferraz semiconductor UL
P. 35

Semiconductor (A) fuses
       Semiconductor (AC) fuses


       American Round Fuses

       Form 101 Range

       A100P





       Semiconductor Protection Fuses

        2
       I t Data – 1000 Volts AC, 100kA
                                                                        1000 VAC     Fault    Load

                                 I t Data
                                 2
                                                                                 Fig. A
           Ampere                       Clearing
           Rating        Melting    @1000VAC (fig A)
                          2
                        (A x10 )
                              3
                                       (A x10 )
                                         2
                                             3
            15            .023            .6
            20            .03             .8                                             2
            25            .047           1.3                               Clearing I t vs. AC
            30            .057           1.5                               Operating Voltage
            35            .29            2.2
            40            .38            2.9
            50            .60            4.5
            60            .86            6.5
            65            1.0            7.6
            70            1.2            8.8
            80            1.5             12
            100           2.4             18
            125           3.8             28
            150           5.4             41
            200           9.6             72                      CORRECTION FACTOR FOR I2T
            225           12              91
            250           15             110
            300           22             160
            350           29             220
            400           38             290
            500           600            450
            600           86             650
            650           100            760
            700           120            880                               OPERATING VOLTAGE (AC RMS VOLTS)
            800           150           1,200
           1,000          240           1,900


                                                                 Watts Loss vs. % Rated Current

       Watts Loss at Rated Current

         Ampere      Watts     Ampere      Watts
          Rating    Loss (W)    Rating    Loss (W)

           15         3.4        225        40
           20         5.9        250        45
           25          9         300        55
           30        12.8        350        65
           35         7.3        400        70             CORRECTION FACTOR FOR WATTS LOSS
           40         8.3        500        90
           50         11         600        110
           60         13         650        120
           70         13         700        125
           80         14         800        140
          100         18        1000        190
          125         23
          150         28
                                                                             PERCENT RATED CURRENT
          200         36


                                                          SCAC35
       12/04
   30   31   32   33   34   35   36   37   38   39   40