Page 7 - IDEC relay catalogue
P. 7
Relays & Sockets RH Series
Specifi cations
Contact Material Silver cadmium oxide
Contact Resistance 1 50mΩ maximum
Minimum Applicable Load 24V DC, 30 mA; 5V DC, 100 mA (reference value)
SPDT 20ms maximum Switches & Pilot Lights
DPDT
Operate Time 2
3PDT 25ms maximum
4PDT
SPDT
DPDT 20ms maximum
Release Time 2
3PDT
4PDT 25ms maximum
SPDT AC: 1.1VA (50Hz), 1VA (60Hz) DC: 0.8W Display Lights
Power Consumption DPDT AC: 1.4VA (50Hz), 1.2VA (60Hz) DC: 0.9W
(approx.) 3PDT AC: 2VA (50Hz), 1.7VA (60Hz) DC: 1.5W
4PDT AC: 2.5VA (50Hz), 2VA (60Hz) DC: 1.5W
Insulation Resistance 100MΩ minimum (500V DC megger)
Between live and dead parts: 2,000V AC, 1 minute
SPDT Between contact and coil: 2,000V AC, 1 minute
Between contacts of the same pole: 1,000V AC, 1 minute
Dielectric Strength 3 Between live and dead parts: 2,000V AC, 1 minute
DPDT
3PDT Between contact and coil: 2,000V AC, 1 minute Relays & Sockets
Between contacts of different poles: 2,000V AC, 1 minute
4PDT Between contacts of the same pole: 1,000V AC, 1 minute
Electrical: 1,800 operations/hour maximum
Operating Frequency
Mechanical: 18,000 operations/hour maximum
Damage limits: 10 to 55Hz, amplitude 0.5 mm
Vibration Resistance
Operating extremes: 10 to 55Hz, amplitude 0.5 mm
2
Damage limits: 1,000m/s (100G)
2
Shock Resistance Operating extremes: 200m/s (20G - SPDT, DPDT)
2
100m/s (10G - 3PDT, 4PDT)
Mechanical Life 50,000,000 operations minimum Timers
DPDT 500,000 operations minimum (120V AC, 10A)
Electrical Life SPDT
3PDT 200,000 operations minimum (120V AC, 10A)
4PDT
SPDT –25 to +50°C (no freezing)
Operating DPDT
Temperature 4 3PDT –25 to +40°C (no freezing)
4PDT
Operating Humidity 45 to 85% RH (no condensation)
Weight (approx.) SPDT: 24g, DPDT: 37g, 3PDT: 50g, 4PDT: 74g Terminal Blocks
Note: Above values are initial values.
1. Measured using 5V DC, 1A voltage drop method
2. Measured at the rated voltage (at 20°C), excluding contact bouncing
Release time of relays with diode: 40 ms maximum
3. Relays with indicator or diode: 1000V AC, 1 minute
4. For use under different temperature conditions, refer to Continuous Load Current vs. Operating Temperature Curve. The operating
temperature range of relays with indicator or diode is –25 to +40°C. Circuit Breakers
USA: 800-262-IDEC Canada: 888-317-IDEC 729