Page 21 - OTDC Switch
P. 21

OTDC XS-SERIES                                                                     21




         —
         Technical data
         OTDC XS-Series IEC and UL












                           —                                                                                           03
                           Technical data according to IEC 60947 for switch-disconnectors OTDC16…32U_
                           Switch size                                      OTDC16U     OTDC25U     OTDC32U
                           Rated insulation voltage Ui  Pollution degree 2  1)  V  1250  1250       1250
                                                     Pollution degree 3  1)  V  1000    1000        1000
                           Rated impulse withstand voltage              kV  8           8           8
          —                Rated thermal current Ith  In open air, normal   A  40       50          63
          OTDC16...32U_                              conditions ²)
                                                     In enclosure 40°C  A   32          40          50
                                                     In enclosure 60°C  A   25          32          40
                           ...with cable or bar cross section  Cu       mm² 4           6           10
                           Rated operational current DC-21B /  660V  One circuit  V  16/2P  25/2P   32/2P
                           Poles in series
                                                             Two circuits  V  16/2Px2   25/2Px2     32/2Px2
                                                             Three circuits  V  16/2Px3  25/2Px3    32/2Px3
                                                     1000V  3)  One circuit  V  10/2P   16/2P       20/2P
                                                             Two circuits  V  10/2Px2   16/2Px2     20/2Px2
                                                             Three circuits  V  10/2Px3  16/2Px3    20/2Px3
                           Rated short-time withstand current,   R.M.S.   kA  1,0       1,0         1,0
                           1000V, 1s                 -value Icw
                           Rated conditional short-circuit   Ip (r.m.s.), 1000V  kA  10  10         10
                           current Ip (r.m.s.)       Max fuse size, gPV  A  80          80          80
                           Power loss / pole         At rated           W   0,1         0,2         0,35
                                                     current
                           Terminal cable size       Cu                 mm² 2.5…16      2.5…16      2.5…16
                           Terminal tightening torque  Counter torque required  Nm  1.2...1.4  1.2...1.4  1.2...1.4
                           Operating torque          2P/4P              Nm  0,4…0,8     0,4…0,8     0,4…0,8
                                                     6P                     0,8…1,9     0,8…1,9     0,8…1,9
                           1) When used with external handle. For use with direct mounted handle, see installation instruction.
                           2) Normal conditions defined in IEC 60947-1, section 6.1.
                           3) U and UT types only (Not applicable for US nor UST).

                           —
                           Technical data in accordance to UL508I for photovoltaic disconnect switches OTDC16…32U_
                           Suitable for use in photovoltaic systems in accordance with article 690 of the NEC.
                           Switch size                                      OTDC16U     OTDC25U     OTDC32U
                           UL Listed                 Standard               UL508i      UL508i      UL508i
                           Rated ambient temperature                    °C  -20…+60     -20…+60     -20…+60
                           Rated current /           600V    One circuit  A  16/2P      25/2P
                           Poles in series                   Two circuits  A  16/2Px2   25/2Px2     32/2Px2
                                                             Three circuits  A  16/2Px3
                           Short circuit rating      600V               kA  5           5           5
                           Protection type           Max fuse size, RK5 fuse  A  80     80          80
                           Wire range                                       AWG 12-6    AWG 12-6    AWG 12-6
                           Technical data according to IEC   See IEC table for type  OTDC16U  OTDC25U  OTDC32U
                           60947