          1 134            ABB  SWITCH-DISCONNECTORS – HIGH PERFORMANCE, COMPACT SOLUTION
                           ABB
                                   C
                                    H
                                  T
                                W
                                  I
          —
          Accessories for manual switch-disconnectors OT160...4000
          Technical data for auxiliary contacts
          Performance data of auxiliary contacts according to IEC 60947-5-1
          For OA1G_, OA3G_                                             For OA1G_, OA3G_
          AC15             DC12                     DC13               U i          690 V
                                           P                P
          U e     I e      U e     I e              I e                U imp        4 kV
          V AC    A        VDC     A       W        A       W          Pollution degree  3
          230     6        24      10      240      2       50         Ith          16 A
          400     4        72      4       290      0.8     60
          415     4        125     2       250      0.55    70         Cable size   1...2 x 0.75...2.5 mm²
          690     2        250     0.55    140      0.27    70         Maximum fuse  16 A / gG
                           440     0.1     44                          NEMA         A600, R300, wire size: 18 - 14 AWG, 1(2)
          Function table of auxiliary contacts
          Handle position         Main contacts           Aux./Test contacts N.O.  Test indication contact N.O.
          Test                    Open                    Closed                  Closed
          0                       Open                    Open                    Open
          I                       Closed                  Closed                  Open
                                                                                             ON
          Handle indications and functions
          •  The handle indicates the position of the main contacts of
           the switch with complete reliability in all situations.
           If the contacts are welded together, the handle
           does not reach the OFF-position but remains
           between ON and OFF, maintaining the door
           interlock and preventing padlocking.
          •  When operating the switch to the TEST-position          OFF
           with a test handle, the test auxiliary contacts change posi-
           tion. The main contacts remain open.
                                                                            Test
   129   130   131   132   133   134   135   136   137   138   139