Page 177 - OT Switch
P. 177

ABB  SWITCH-DISCONNECTORS – HIGH PERFORMANCE, COMPACT SOLUTION
                                                                                                              7
                           ABB    S W I T C H - D I S C O N N E C T O R S  –  H I G H  P E R F OR M A NC E,  C OM P A C T  S OL UT I ON    1 177 7


          —
          Accessories for motorized switch-disconnectors

          Ordering information for auxiliary contacts



                                    —
                                    Auxiliary contacts for OTM40...4000, IP20
                                    Contact numbering according to EN 50013. Types _AU have gold plated contacts for harsh
                                    environments and low operating voltages. Auxiliary contacts are mountable on right side in
                                    types OTM40…4000 or under the mechanism cover in types OTM160…4000. Early break
                                    type auxiliary contacts means that in the switches, the NO aux.contacts break before
                                    the main contacts open.
          OA1G10, OA8G01, OA3G01
                                                                                                                       04
                                    In types with auxiliary contacts mountable under the mechanism cover,  the “test” contacts
                                    operate in ON- and OFF-positions as well as when the handle is turned to TEST-position (45°
                                    over the OFF-position). The “test indication” contacts operate only when the handle is
                                    turned to TEST-position. The OA1G10 (N.O.) or OA3G01 (N.C.) auxiliary contact blocks can be
                                    used as standard auxiliary contacts, “test” or “test indication” contacts. The desired func-
                                    tions are achieved when an auxiliary contact block is installed in a specific place.

                                    See next pages for performance data, functions and contact timing.
                                                                                                          Weight/
         OA2G11
                                    Suitable                                                                 unit
                                    for switches    Function                      Type            Order code  kg
                                    Mounting on the right side OTM40…125
          13
                                    Maximum 2 auxiliary contact blocks, snap-on mounting
            1 no                    OTM40…125       1NO, early break            OA1G10      1SCA022353R4970  0.03
          14                        OTM40..125      1NC, early make            OA8G01       1SCA022744R2240   0.03
                                    OTM40…125       1NO, early break          OA1G10AU      1SCA022436R7910  0.03
          1NO
                                    OTM40...125F3   1NO+1NC, simultaneous      OA2G11       1SCA022379R8100  0.03
                                                    function
         21                                         with the main contacts
                                    Mounting on the right side OTM160…4000:
            1 nc
                                    Maximum 2+2 auxiliary contact blocks (N.O. or N.C.), snap-on mounting.
         22                         OTM160…4000     1NO, early break            OA1G10      1SCA022353R4970  0.03
         1NC                        OTM160…4000     1NC, early make            OA3G01       1SCA022456R7410  0.03
                                    OTM160…4000     1NO, early break          OA1G10AU      1SCA022436R7910  0.03
                                    OTM160…4000     1NC, early make          OA3G01AU       1SCA022819R5260  0.03
                                    Mounting under the mechanism cover OTM160…4000:
                                    See next page for maximum number of contact blocks, “Aux./test” contacts and “test indication”.
                                    OTM160…4000     1NO, early break            OA1G10      1SCA022353R4970  0.03
                                    OTM160…4000     1NC, early make            OA3G01       1SCA022456R7410  0.03
                                    OTM160…4000     1NO, early break          OA1G10AU      1SCA022436R7910  0.03
                                    OTM160…4000     1NC, early make          OA3G01AU       1SCA022819R5260  0.03



                                    Mounting under the mechanism cover,   Maximum number   Aux./Test    Test indication
                                    OTM160…4000:                         of contact blocks contacts  contacts
                                    OTM160...250                         2            2            -
                                    OTM315...400                         4            -            2
                                    OTM630...800                         4            -            2
                                    OTM 1000...4000                      6            2  1)        4
                                    1)  Early operation test contact
   172   173   174   175   176   177   178   179   180   181   182