Page 130 - Sace Emax 2 Catalogue
P. 130
6/28 SACE EMAX 2 LOW VOLTAGE AIR CIRCUIT-BREAKERS
—
Accessories for Ekip trip units
Displaying and supervision
Ekip Multimeter (Fig. 43)
Ekip Multimeter is a display unit to be installed on the front of the switchgear for SACE Emax 2 cir-
cuit-breakers equipped with Ekip electronic trip units. The device is equipped with a large touch screen
display and enables measurements to be displayed with the same levels of precision. If connected to
trip units with a display, Ekip Multimeter enables the adjustment of parameters and protection thresh-
olds. Up to 4 Ekip Multimeter devices can be connected at the same time to the same Ekip protection
trip unit to display currents, voltage, powers and energy.
—
Fig. 43
Ekip Multimeter can be powered either in direct current or in alternating current. It is equipped with a
24V DC output that supplies the trip unit to which it is connected.
Power supply 24-48V DC, 110-240V AC/DC
Tolerance 21.5-53V DC, 105-265V AC/DC
Rated Power 10VA/W
Inrush current 2A for 20ms
Ekip Control Panel on front of switchgear (Fig. 44)
The Ekip Control Panel enables the SACE Emax 2 circuit-breakers connected to the Ekip Link system to
be controlled and monitored.
The panel is supplied already equipped with supervision software and requires no programming. Ekip
Control Panel requires a 24V DC power supply and is equipped with:
• 2 RJ45 EtherNet ports for connection to the Ekip Link system and to the local network for remote con-
trol via web server option
— • 1 RS485 serial port for integration of the Modbus network if it is to be used with circuitbreakers of
Fig. 44
the Tmax series
• 4 USB ports for downloading data.
Lite panel (Fig. 45)
The Lite Panel is a 7 inches local control panel that can monitor and control max 15 devices connected
via Modbus TCP/IP or Modbus RTU.
The most important functionalities of this device:
• User administration: 5 level of user present inside the Lite Panel
— • Automatic Scan via Modbus RTU and via Modbus TCP connection of various devices already mapped
Fig. 45
Colors ABB S.p.A ABB SACE Division
Doc. N°: xxxx
Red Pantone 032c inside the Lite panel: Emax 2, Tmax XT, ITS2, M4M, CMS700 etc… (see detailed list in the user installa-
Product Name: xxxx
Title: Front Label
tion manual)
DESIGN GROUP ITALIA 29 Maggio 2019
• Local monitoring directly on the front of the panel for all the devices
• Local control of devices: open, closing, reset
• Alarm list and event log directly visible from one access point