       2 - Measurements



                               List Ekip Dip is able to take various measurements, all available via Ekip Connect::
                                     Parameter          Description
                                     Instantaneous currents  Phase current and earth fault measurements in real time
                                     Trip               List of current protection trips (TRIP)
                                     Min Max Measurements  History of minimum and maximum currents, recorded at a settable interval
                                     Operation counters  Number of mechanical and electrical operations

                                    All information are available via the Ekip T&P module and via Ekip Connect software; instantaneous
                                    measurements are also available via the Ekip Multimeter unit.



              Instantaneous currents The instantaneous currents, available in the Measurements pages, are real time measurements of the phase
                                    and earth fault currents expressed in root mean square value; the measurement time and performance
                                    depend on the rated current defined by the Rating plug (In):
                                                                    Monitor time    Normal         Accuracy of
                                     Measurement
                                                                    (min-max)       operating range  value read  (1)
                                     Phase currents                 0,004...64 In   0,2...1,2 In   1 %
                                     Internal earth fault currents  (2)  0,08...64 In  0,2...1,2 In  2 %

                                    (1)  the accuracies refer to normal operating ranges, as established by IEC 61557-12
                                    (2)  available with LSIG versions


              Maximum and minimum  The trip unit is able to record the maximum and minimum current, measured inside an interval that can be
                           currents programmed by the user.
                                    Every measurement recorded is accompanied by the following information:
                                     •  Recording interval.
                                     •  Phase and value of maximum and minimum current measured.
                                     •  Date and time of the recording (referring to the internal clock).
                                           NOTE: in the case of the minimum current, if the value drops below the 0.03 In threshold, it
                                               will be recorded and represented by the symbol “…” in the measurement field.



                              Trips The trip unit is able to record the last 30 openings of the circuit-breaker caused by protection functions (trips).
                                    The trips include useful information:
                                     •  The protection that caused the trip
                                     •  The progressive number of the opening
                                     •  The date and time of the opening (referring to the internal clock)
                                     •  The measurements associated to the trip protection.


                      Contact Wear Contact wear indicates the state of deterioration of the main contacts of the circuit-breaker.
                                    The value is expressed as a percentage, and is 0 % in the case of no wear, and 100 % in the case of total
                                    wear.
                                    The contact wear is calculated automatically by the trip unit at every opening for protection or, in the presence
                                    of an auxiliary power supply, also at every manual opening of the circuit-breaker.


               Number of operations In the presence of auxiliary power, the trip unit records a series information relating to the openings of the
                                    circuit-breaker:
                                     •  Number of manual operations
                                     •  Total number of operations (manual + trips)