Page 15 - Surge-Protection-E_0.pdf
P. 15

DEHNselect SPD Tool – Planning of internal Lightning Protection and Surge Protection

           Practice-oriented – Professional – User-friendly     DEHNselect SPD is easy to use and requires no special knowledge or train-
           Find the right product quickly and easily with the help of our   ing. The user-friendly surface facilitates operating the program.
           surge protection assistants for power supply and information   This electronic planning and selection aid provides easy and practice-ori-
           technology systems.                                  ented support for, e.g. designers, electricians and installers of lightning
           The new DEHNselect SPD software module allows you to define and se-  protection systems, thus making it considerably easier to professionally
           lect all necessary internal lightning protection and surge protection prod-  implement a surge protection concept.
           ucts. It creates a structure plan including a bill of materials and allows   For more detailed information, see brochure DS 709 E (DEHNsupport Tool-
           fast online access to all documents for the products selected such as data   box) or visit www.dehn-international.com/en/selection-guides-and-con-
           sheets and installation instructions.                figurators.
























           Filter function allows easy product selection





                                                         Product comparison




                                                         Product Data Sheet: DEHNventil® modular
                                                         DV M TNS 255 FM (951 405)
                                                          ■ Prewired spark-gap-based type 1 and type 2 combined lightning current and surge arrester consisting of a base part and plug-in protection
                                                           modules
                                                          ■ Maximum system availability due to RADAX Flow follow current limitation
                                                          ■ Capable of protecting terminal equipment
                                                          Figure without obligation
                                                                     Basic circuit diagram DV M TNS 255 FM  Dimension drawing DV M TNS 255 FM
                                                         Modular combined lightning current and surge arrester for TN-S systems.
                                                         Type               DV M TNS 255 FM
                                                         Part No.            951 405
                                                         SPD according to EN 61643-11 / IEC 61643-11  type 1 + type 2 / class I + class II
                                                         Energy coordination with terminal equipment (≤ 5 m)  type 1 + type 2 + type 3
                                                         Nominal voltage (a.c.) (U N )  230 / 400 V (50 / 60 Hz)
                                                         Max. continuous operating voltage (a.c.) (U C )  264 V (50 / 60 Hz)
                                                         Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (I total )  100 kA
           Bill of materials                             Specific energy [L1+L2+L3+N-PE] (W/R)  2.50 MJ/ohms
                                                                             25 kA
                                                         Lightning impulse current (10/350 µs) [L, N-PE] (I imp )
                                                         Specific energy [L,N-PE] (W/R)
                                                                            156.25 kJ/ohms
                                                         Nominal discharge current (8/20 µs) [L/N-PE]/[L1+L2+L3+N-PE]
                                                         (I n )              25 / 100 kA
                                                         Voltage protection level [L-PE]/[N-PE] (U P )  ≤ 1.5 / ≤ 1.5 kV
                                                         Follow current extinguishing capability (a.c.) (I fi )  50 kA rms
                                                         Follow current limitation / Selectivity  no tripping of a 20 A gG fuse up to 50 kA rms  (prosp.)
                                                         Response time (t A )  ≤ 100 ns
                                                         Max. backup fuse (L) up to I K  = 50 kA rms  315 A gG
                                                         Max. backup fuse (L-L')  125 A gG
                                                         Temporary overvoltage (TOV) [L-N] (U T ) – Characteristic  440 V / 120 min. – withstand
                                                         Operating temperature range [parallel] / [series] (T U )  -40 °C ... +80 °C / -40 °C ... +60 °C
                                                         Operating state / fault indication  green / red   Product Data Sheet: BLITZDUCTOR® XT – Protection Modules with

                                                         Number of ports      1    LifeCheck®
                                                         Cross-sectional area (L1, L1', L2, L2', L3, L3', N, N', PE, 9) (min.)  10 mm 2  solid / flexible
                                                         Cross-sectional area (L1, L2, L3, N, PE) (max.)  50 mm 2  stranded / 35 mm 2  flexible   BXT ML4 B 180 (920 310)

                                                         Cross-sectional area (L1', L2', L3', N', 9) (max.)  35 mm 2  stranded / 25 mm 2  flexible
                                                         For mounting on   35 mm DIN rails acc. to EN 60715   ■ LifeCheck SP  D monitoring function

                                                         Enclosure material  thermoplastic, red, UL 94 V-0   ■ Four-pole lightning equipotential bonding
                                                         Place of installation  indoor installation   ■ For installation in conformity with the lightning protection zone concept at the boundaries from 0 A  – 1 and higher

                                                         Degree of protection  IP 20
                                                         Capacity           8 module(s), DIN 43880
                                                         Approvals          KEMA, VDE, UL, VdS
                                                         Type of remote signalling contact  changeover contact
                                                         Switching capacity (a.c.)  250 V / 0.5 A
                                                         Switching capacity (d.c.)  250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
                                                         Cross-sectional area for remote signalling terminals  max. 1.5 mm 2  solid / flexible
                                                                         Use in switchgear installations with prospective short-circuit
                                                         Extended technical data:  currents of more than 50 kA rms  (tested by the German VDE)  Figure without obligation
                                                         – Max. prospective short-circuit current  100 kA rms  (220 kA peak )       Basic circuit diagram BXT ML4 B 180  Dimension drawing BXT ML4 B 180
                                                         – Limitation / Extinction of mains follow currents  up to 100 kA rms  (220 kA peak )    Space-saving four-pole lightning current arrester module with LifeCheck feature for almost all types of applications. For use in connection with

                                                                                   downstream Q surge arresters or combined lightning current and surge arresters with a lower or equal voltage level. If LifeCheck detects thermal

                                                         – Max. backup fuse (L) up to I K  = 100 kA rms  315 A gG  or electrical overload, the arrester has to be replaced. This status is indicated contactlessly by the DEHNrecord LC / SCM / MCM reader.
                           Structure plan                Weight              85363030  Type           BXT ML4 B 180
                                                                             1,36 kg
                                                         Customs tariff number
                                                                                   Part No.
                                                                                                      920 310
                                                         PU GTIN            4013364108165  SPD monitoring system    LifeCheck
                                                                             1 pc(s)
                                                                                   SPD class
                                                                                                       H
                                                                                   Nominal voltage (U N )  180 V
                                                                                   Max. continuous operating voltage (d.c.) (U C )  180 V
                                                         We reserve the right to introduce changes in performance, configuration and technology, dimensions, weights and materials in the course of technical progress. The figures are shown without obligation.  127 V
                                                                                   Max. continuous operating voltage (a.c.) (U C )
                                                                                   Nominal current at 45 °C (I L )  1.2 A
                                                                                   D1 Total lightning impulse current (10/350 µs) (I imp )  10 kA
                                                           © DEHN + SÖHNE GmbH + Co. KG · Hans-Dehn-Str. 1 · Postfach 1640 · D-92306 Neumarkt · Tel. +499181 906-0 · www.dehn.de  2.5 kA
                                                                                   D1 Lightning impulse current (10/350 µs) per line (I imp )
                                                         3,  : Tested +: New (: Discontinued Model  C2 Total nominal discharge current (8/20 µs) (I n )  20 kA
                                                                                   C2 Nominal discharge current (8/20 µs) per line (I n )  10 kA
                                                          tested
                                                                                   Voltage protection level line-line for I imp  D1 (U p )  ≤ 600 V
                                                         Product data sheet        Voltage protection level line-PG for I imp  D1 (U p )  ≤ 550 V
                                                                                   Voltage protection level line-line at 1 kV/µs C3 (U p )
                                                                                                       ≤ 650 V
                                                                                   Voltage protection level line-PG at 1 kV/µs C3 (U p )  ≤ 550 V
                                                                                   Series resistance per line  0.4  ohm(s)
                                                                                   Capacitance line-line (C)  ≤ 16 pF
                                                                                   Capacitance line-PG (C)  ≤ 16 pF
                                                                                   Operating temperature range (T U )  -40 °C ... +80 °C
                                                                                   Degree of protection (with plugged-in protection module)  IP 20
                                                                                   Pluggable into   BXT BAS / BSP BAS 4 base part
                                                                                   Earthing via     BXT BAS / BSP BAS 4 base part
                                                                                   Enclosure material  polyamide PA 6.6
                                                                                   Colour              yellow
                                                                                   Test standards   IEC 61643-21 / EN 61643-21, UL 497B
                                                                                   Approvals      CSA, VdS, EAC, ATEX, IECEx, CSA & USA Hazloc, SIL
                                                                                   SIL classification  up to SIL3 * )
                                                                                   ATEX approvals  DEKRA 11ATEX0089 X: II 3 G Ex nA IIC T4 Gc
                                                                                   IECEx approvals  DEK 11.0032X: Ex nA IIC T4 Gc
                                                                                   CSA & USA Hazloc approvals (1)  2516389: Class I Div. 2 GP A, B, C, D T4
                                                                                   CSA & USA Hazloc approvals (2)  2516389: Class I Zone 2, AEx nA IIC T4
                                                                                   Weight              25 g
                                                                                   Customs tariff number  85363010
                                                                                   GTIN               4013364109124
                                                                                   PU                  1 pc(s)
                                                                                   * )  For more detailed information, please visit www.dehn-international.com.
                                                                                   We reserve the right to introduce changes in performance, configuration and technology, dimensions, weights and materials in the course of technical progress. The figures are shown without obligation.
                                                                                     © DEHN + SÖHNE GmbH + Co. KG · Hans-Dehn-Str. 1 · Postfach 1640 · D-92306 Neumarkt · Tel. +499181 906-0 · www.dehn.de
                                                                                   3,  : Tested +: New (: Discontinued Model
                                                                                   tested
                                                                                  Product data sheet
                                                                                                               13
   10   11   12   13   14   15   16   17   18   19   20