Page 44 - index
P. 44
Technical Resources
1. TECHNICAL SPECIFICATIONS OF TECHNO MODULE SYSTEM
GENERAL DATA
Installation Indoor
Floor standing
Mounting possibilities
Wall mounting
RAL 7032 Smooth / Semi Gloss
Colour RAL 2000 Smooth / Semi Gloss
Other colours by request
Type Epoxy Polyester Powder
Coating
Thickness ≥ 60μm
MECHANICAL DATA
Front only
Service access
Front & Rear
Top
Cable entry
Bottom
Field/Tier Arrangement Front connected / Back to Back
Fixed
Compartments Removable
Withdrawable
Degree of protection (IP code) Techno Module up to IP55
Mechanical impact (IK code) Techno Module IK10
Form of internal separation As per AS61439.2 up to 4b
1000 cycles
Mechanical operation Techno Module
200 cycles
Length Up to 2400 mm (can be extended)
Recommended dimensions of
Height Up to 2400 mm (can be extended)
transport section
Depth Up to 2400 mm (can be extended)
ELECTRICAL DATA
Rated operational voltage (U ) up to 1000 V
e
Rated insulation voltage (U ) up to 1000 V
i
Rated impulse withstand voltage (U ) up to 12 kV
imp
Rated frequency (f) up to 60 Hz
0
Techno Module up to 12000 A at 35 C
(main busbar) up to 10000 A at 50 C
0
Rated current (I )
n
0
Techno Module 1 up to 6300 A at 35 C
(functional unit)
0
up to 5650 A at 50 C
up to 120 kA - 1s
Rated short-time withstand
Techno Module
current (I )
cw up to 100 kA - 3s
up to 100 kA at 415 V
up to 100 kA at 690 V
Rated conditional short circuit Techno Module
current (I ) 1 up to 100 kA at 800 V
cc
up to 90 kA at 900 V
Pollution degree 3
Earthing system TN-S, TN-C, TN-C-S, TT, IT
44 1300 556 601 | ipd.com.au | TM-R01