         4. FORMS OF INTERNAL SEPARATION AS PER BS EN 61439-2

          Form 1                   Form 2                   Form 3                    Form 4
                                                           Separation of busbars from the  Separation of busbars from the
                                                           functional units and separation   functional units and separation of all
                                                           of all functional units from one   functional units from one another,
                                  Separation of busbars from the
                No separation                              another. Separation of the   including the terminals for external
                                  functional units.
                                                           terminals for external conductors   conductors from functional units,
                                                           from functional units, but not from   which are an integral part of the
                                                           each other.               functional unit.
                                  Form 2a                  Form 3a                   Form 4a Type 1







                                  Sub-criteria “a”: terminals for   Sub-criteria “a”: terminals for   Type 1: Busbar separation is achieved
                                  external conductors not separated  external conductors not separated  by insulated covering, e.g. sleeving,
                                  from busbars.            from busbars.             wrapping or coatings. Cables may be
                                                                                     glanded elsewhere.



                                  Form 2b Type 1           Form 3b Type 1            Form 4a Type 2 & Type 3






                                                                                                                    5
                                  Sub-criteria “b”: terminals for   Sub-criteria “b”: terminals for   Type 2: Busbar separation is by
                                  external conductors separated   external conductors separated   metallic or non-metallic rigid barriers
                                  from busbars.            from busbars.             or partitions. Cables may be glanded
                                                                                     elsewhere.
                                  Type 1: Busbar separation is   Type 1: Busbar separation is  Type 3: Busbar separation is by
                                  achieved by insulated covering,  achieved by insulated covering,  metallic or non-metallic rigid barriers
                                  e.g. sleeving, wrapping or coatings. e.g. sleeving, wrapping or coatings. or partitions. The termination for each
                                                                                     functional unit has its own integral
                                                                                     glanding facility.



                                  Form 2b Type 2           Form 3b Type 2            Form 4b Type 4








                                  Type 2: Busbar separation is by  Type 2: Busbar separation is by  Sub-criteria “b”: terminals for external
                                  metallic or non-metallic rigid   metallic or non-metallic rigid   conductors not in the same
                                  barriers or partitions.  barriers or partitions.   compartment as the associated
                                                                                     functional unit, but in individual,
                                                                                     separate, enclosed protected spaces
                                                                                     or compartments.
                                                                                     Type 4: Busbar separation is achieved
                                                                                     by insulated covering, e.g. sleeving,
                                                                                     wrapping or coatings. Cables may be
                                                                                     glanded elsewhere.


         All information shall be treated as guidance only. ELSTEEL does not take any responsibility.
         Always check with the latest edition of BS EN 61439 or equivalent.