Page 132 - V16 Catalogue Final
P. 132

LOAD BREAK SWITCHES - 1000V
           160 TO 800A


                                               3 POLE - FRONT OPERATED
                                               INCLUDING DOOR HANDLE AND OPERATING SHAFT

          Features:                                                                         Cable Section
          - Complete with Shaft & Handle.       Open air thermal  Rated Operational Current  Short CCT  Enclosed @
          - Handle interlock defeatable.        current (Ith)  AC21A  AC22A  AC23A  Rating   Rated Current
          - Up to 3 Padlocks.                   (A)        1000V AC  1000V AC  1000V AC  RMS/SEC  (mm )  Part No.
                                                                                              2
          - Can be locked “ON” (with modification).
          - Optional wide phase centres.        Base Mount - Mechanism on the Left
                                                200        160      160     135     8       70       OT160EV03P
                                                200        200      200     135     8       95       OT200E03P
                                                250        250      250     135     8       120      OT250E03P
                                                315        315      315     200     15      185      OT315E03P
                                                400        400      400     200     15      240      OT400E03P
                                                630        630      630     400     20      2 x 185  OT630E03P
                                                800        800      800     400     20      2 x 240  OT800E03P
                                                Base Mount - Mechanism Between Poles
                        OT315E03P
                                                200        160      160     135     8       70       OT160EV12P
                                                200        200      200     135     8       95       OT200E12P
                                                250        250      250     135     8       120      OT250E12P
                                                315        315      315     200     15      185      OT315E12P
                                                400        400      400     200     15      240      OT400E12P
                                                630        630      630     400     20      2 x 185  OT630E12P
                                                800        800      800     400     20      2 x 240  OT800E12P
                        OT250E12P






                                               4 POLE - FRONT OPERATED
                                               INCLUDING DOOR HANDLE AND OPERATING SHAFT
          Features:                                                                         Cable Section
          - Complete with Shaft & Handle.       Open air thermal  Rated Operational Current  Short CCT  Enclosed @
          - Handle interlock defeatable.        current (Ith)  AC21A  AC22A  AC23A  Rating   Rated Current
          - Up to 3 Padlocks.                   (A)        1000V AC  1000V AC  1000V AC  RMS/SEC  (mm )  Part No.
                                                                                              2
          - Can be locked “ON” (with modification).
          - Optional wide phase centres.        Base Mount - Mechanism on the Left
                                                200        160      160     135     8       70       OT160EV04P
                                                200        200      200     135     8       95       OT200E04P
                                                250        250      250     135     8       120      OT250E04P
                                                315        315      315     200     15      185      OT315E04P
                                                400        400      400     200     15      240      OT400E04P
                                                630        630      630     400     20      2 x 185  OT630E04P
                                                800        800      800     400     20      2 x 240  OT800E04P
                        OT250E04P               Base Mount - Mechanism Between Poles
                                                200        160      160     135     8       70       OT160EV22P
                                                200        200      200     135     8       95       OT200E22P
                                                250        250      250     135     8       120      OT250E22P
                                                315        315      315     200     15      185      OT315E22P
                                                400        400      400     200     15      240      OT400E22P
                                                630        630      630     400     20      2 x 185  OT630E22P
                                                800        800      800     400     20      2 x 240  OT800E22P
                        OT250E22P











    124   V16-PD-I&S-R02                                www.ipd.com.au                             Phone: 1300 556 601
   127   128   129   130   131   132   133   134   135   136   137