Page 292 - V16 Catalogue Final
P. 292
METER SELECTION CHART - SOCOMEC
Single-phase Single-phase Three-phase Three-phase Three-phase
Network - Input current Direct 40A Direct 80A Direct 80A Direct 100A CT Connect .../5A
Active energy meters:
COUNTIS E E00 E03 E11 E13 E17 E21 E23 E27 E30 E33 E41 E43
References 48503058 48503039 48503060 48503043 48503047 48503062 48503050 48503054 48503005 48503012 48503063 48503065
Main Specifications:
RS485 Modbus RTU - • - • - - • - - • - •
Ethernet Modbus TCP/RTU - - - - • - - • - - - -
Width (17.5mm) 1 module 1 module 2 modules 2 modules 2 modules 4 modules 4 modules 4 modules 7 modules 7 modules 4 modules 4 modules
Functions:
Total/partial energy kWh •/• •/• •/• •/• •/• •/• •/• •/• • • •/• •/•
Active power (kW) • • • • • • • • • • • •
Reactive power (kVAr) • • • • • • • • - via COM • •
up to 4 via up to 4 via
Tariff for kWh - Dual Dual Dual Dual Dual Dual Dual - Dual
COM COM
Total/partial energy kVArh •/• •/• •/• •/• •/• • •/• •/• - via COM •/• •/•
Apparent energy (kVA) - via COM - • • • • • - via COM • •
Load curve - - - - - - - - - via COM - via COM
Measurement (I, V, P, Q, S, • • • • • • • • - via COM • •
F and PF)
CT connection indication - - - - - - - - - - • •
Birectional (energy -
consumption and production) • • • • • • • • • • •
Integrated web server - - - - • - - • - - - -
Compatibility with Webview - • - • • - • • - • - •
Accuracy:
Active energy (IEC 62053-21) class 1 class 1 class 1 class 1 class 1 Class 1 class 1 class 1 class 1 class 1 class 1 class 1
Reactive energy (according to
IEC 62053-23) class 2 class 2 class 2 class 2 class 2 Class 2 class 2 class 2 - - class 2 class 2
Characteristics:
Metrological LED • • • • • • • • • • • •
Pulse output / Alarm 100 Wh 100 Wh 100 Wh 100 Wh - 100 Wh 100 Wh 100 Wh - - config. config.
Phase/neutral inversion
protection - - - - - - - - • • - -
284 V16-PM-R04 www.ipd.com.au Phone: 1300 556 601