MOULDED CASE CIRCUIT BREAKERS
           TMAX XT EMBEDDED METERING CLASS 1
           With the Ekip Touch trip units,  the embedded measurement functionalities allow the measurement of power and energy to a Class 1 degree of accuracy, as specified by the
           IEC 61557-12 Standard, avoiding the need of additional devices, saving costs, space and installation time.

                                               EKIP LSI ELECTRONIC TRIP UNIT + MEASURING PACKAGE + CLASS 1
                                               METERING
                                               (COMPLETE UNIT)
                                                             Current    L-I1       S-I2       I-I3
                                                 Frame Size  Rating In (A)  0.4 to 1 x In (A) 0.6 to 10 x In (A) 1.5 to 10 x In (A) Part No.
                                                3 POLE
                                                              100      40-100    60-1000    150-1000  XT2N3T100MC1
                                                   XT2
                                                              160      64-160    96-1600    240-1600  XT2N3T160MC1
                                              36kA  XT4       100      40-100    60-1000    150-1000  XT4N3T100MC1
                                                                       64-160
                                                                                 96-1600
                                                                                            240-1600
                                                                                                     XT4N3T160MC1
                                                              160
                                                              250      100-250   150-2500   375-2500  XT4N3T250MC1
                                                              400      160-400   240-4000   600-4000  XT5N3T400MC1
                                                   XT5
                     XT5N3T630MC1                             630      252-630   378-6300   945-6300  XT5N3T630MC1
                                                3 POLE
                                                              100      40-100    60-1000    150-1000  XT2H3T100MC1
                                                   XT2
                                                              160      64-160    96-1600    240-1600  XT2H3T160MC1
                                              70kA  XT4       100      40-100    60-1000    150-1000  XT4H3T100MC1
                                                                                                     XT4H3T160MC1
                                                                                            240-1600
                                                                                 96-1600
                                                              160
                                                                       64-160
                                                              250      100-250   150-2500   375-2500  XT4H3T250MC1
                                                              400      160-400   240-4000   600-4000  XT5H3T400MC1
                                                   XT5
                     XT5H3T630MC1                             630      252-630   378-6300   945-6300  XT5H3T630MC1




                                                             Current    L-I1       S-I2       I-I3
                                                 Frame Size  Rating In (A)  0.4 to 1 x In (A) 0.6 to 10 x In (A) 1.5 to 15 x In (A) Part No.
                                                3 POLE
                                                              800
                                                                                 480-8000
                                                                       320-800
                                              50kA  XT7      1000     400-1000   600-10000  1200-12000  XT7S3T800MC1
                                                                                                     XT7S3T1000MC1
                                                                                           1500-15000
                     XT7S3T800MC1                            1250     500-1250   750-12500  1875-18750  XT7S3T1250MC1
                                                             1600     640-1600   960-16000  2400-24000  XT7S3T1600MC1
                                                3 POLE
                                                              800      320-800   480-8000  1200-12000  XT7H3T800MC1
                                              70kA  XT7      1000     400-1000   600-10000  1500-15000  XT7H3T1000MC1
                                                                                                     XT7H3T1250MC1
                                                                                           1875-18750
                                                                      500-1250
                                                                                 750-12500
                                                             1250
                                                             1600     640-1600   960-16000  2400-24000  XT7H3T1600MC1
                                               - Class 1 available for breakers 100A and above only.
                                               - For communication modules, please refer to accessories section.
                     XT7H3T800MC1














     52   V16-PD-MCCB-R04                               www.ipd.com.au                             Phone: 1300 556 601