ABB | SACE Tmax XT

                      Synchrocheck With regard to closing the interconnection switch, the  Ekip Synchrocheck module recognizes and
                                    reports whether there are synchronism conditions between two independent voltage sources (example:
                                    generator + grid).
                                    A description of the module, the protection function and performance is given in the chapter dedicated
                                    to the modules (page 159).


        Programmable Functions and  Eight commands are available, with activation that can be programmed on the basis of signals or events.
                        Commands Distributed among different Ekip Touch menus, the commands are:
                                     Name               Description                            Path (page)
                                     External Trip      Sends a TRIP command
                                     Trip RESET         Reset of the trip signal               Advanced - Functions
                                                                                               (27)
                                     Turn on SET B      Changes the protections set, from Set A to Set B
                                                        It activates 2I protection, if configured for this   Advanced - Functions -
                                     2I Mode
                                                        function                               2I Menu (42)
                                                                                               Measurements - Energy
                                     RESET Energy       Resets the energy meters
                                                                                               (28)
                                     YO Command         Sends an open command  (1)             Settings - Functions (
                                     YC Command         Sends a close command  (1)             29)
                                                        Changes the configuration, from Remote to
                                     LOCAL Switch On                                           Settings - Modules
                                                        Local
                                     Signaling RESET    Reset the contacts of the signalling modules  -Functions (29)

                                    (1)  the MOE-E storage command must be present
                                    Parameters
                                    Each command provides two programming parameters:

                                     Parameter    Description                                         Default
                                                  Event or several command activation events (up to eight, in AND
                                     Function     or OR logic configuration). The Custom configuration can be   Deactivated
                                                  programmed via Ekip Connect.
                                                  This is the minimum time the expected event must be present in
                                     Delay        order to activate the command; the value is given in seconds and  0 s
                                                  can be set within a range: 0 s to 100 s, in 0.1 s steps

                                           IMPORTANT: the commands are sent if all the operating conditions expected by the unit
                                           are present (connections, power supplies, alarms, etc.)