Page 279 - dehn-catalogue-lightning-protection_3
P. 279
Equipotential Bonding
UNI Earthing Clamps
For integrating the mounting systems, e.g. of PV installations in the functional equipotential bonding / functional earthing (black conductor
possible) and lightning equipotential bonding.
The StSt contact plate (intermediate element) allows different conductor materials (Cu, Al, St/tZn and StSt) to be connected to the usual
mounting systems, e.g. to aluminium, without the risk of contact corrosion.
With M8 hammer-head bolt and self-locking nut 540 250 UEK 8.10 AQ4 50 HKSM8 V2A
Part No. 540 250
540 250 pc(s) 5,53 € 4013364138650 01 04 01 02 60 g 50
Material of clamp StSt
Clamping range Rd 8-10 mm
Connection (solid / stranded) 4-50 mm 2
Screw hammer-head bolt M8 x 30 mm
Material of screw / nut StSt
Standard EN 62561-1
PU 50 pc(s)
With M10 hammer-head bolt and self-locking nut 540 260 UEK 8.10 AQ4 50 HKSM10 V2A
Part No. 540 260
540 260 pc(s) 5,93 € 4013364138667 01 04 01 02 60 g 50
Material of clamp StSt
Clamping range Rd 8-10 mm
Connection (solid / stranded) 4-50 mm 2
Screw hammer-head bolt M10 x 30 mm
Material of screw / nut StSt
Standard EN 62561-1
PU 50 pc(s)
Contact plate and double clamp (separate) with square hole for M8 screw 540 251 KP AQ4 50 DUL 8.10 VKL9 V2A
Part No. 540 251
540 251 pc(s) 3,55 € 4013364138674 01 04 01 02 37 g 10
Material of clamp StSt
Clamping range Rd 8-10 mm
Connection (solid / stranded) 4-50 mm 2
Standard EN 62561-1
PU 10 pc(s)
Contact plate and double clamp (separate) with square hole for M10 screw 540 261 KP AQ4 50 DUL 8.10 VKL11 V2A
Part No. 540 261
540 261 pc(s) 3,58 € 4013364138681 01 04 01 02 36 g 10
Material of clamp StSt
Clamping range Rd 8-10 mm
Connection (solid / stranded) 4-50 mm 2
Standard EN 62561-1 Equipotential Bonding
PU 10 pc(s)
6
Protective Spark Gap
Protective spark gap in closed design with plastic sheath for indirect connection of an overhead line roof pole to the external lightning
protection system.
DSFS 920 000 DSFS
Plastic-insulated protective spark gap for indirect connection of an overhead line roof pole to the external lightning protection system.
920 000 4013364057494 04 01 05 01 127 g 1
pc(s) 20,60 €
Type DSFS
Part No. 920 000
100% lightning impulse sparkover voltage (1.2/50 µs) (Urimp) ~ 25 kV
Nominal discharge current (8/20 µs) (In) 25 kA
Power frequency sparkover voltage (50 Hz) (Uaw) ~ 10 kV
PU 1 pc(s)
Valid as of March 1, 2020 Detailed product information can be found on our website 275