Page 138 - dehn-catalogue-safety-equipment_0
P. 138
DEHNcare ® APC, APJ, APT DEHNcare ® APG DEHNcare ® APHO DEHNcare ® ESH U S, APS Arc Fault Protection System Water Jet Protection
Active Arc Fault Protection
Detection Device (Current + Light)
782 030 DSRT DD CPS BACA
782 031 DSRT DD CPS AACA
DSRT DD CPS .... detection device for current and light detection (DSRT PS point sensors) including output for directly connecting two DSRT
782 030 4013364245792 05 02 10 02 1.19
kg 0,00 € QD / DSRT QD II quenching devices.
782 031 4013364245815 05 02 10 02 1.19
kg 0,00 €
Type DSRT ... DD CPS BACA DD CPS AACA
Part No. 782 030 782 031
Min. / max. voltage (UN) 18-72 V d.c. 92-265 V AC / DC
Degree of protection (front side) IP 50 IP 50
Degree of protection (rear side) IP 20 IP 20
Dimensions of the front plate (H x W) 177 x 102 mm 177 x 102 mm
Mounting dimensions (H x W x D) 157 x 82 x 164 mm 157 x 82 x 164 mm
S1, S2, S3, S4 (3 sensors (DSRT PS) S1, S2, S3, S4 (3 sensors (DSRT PS)
Sensor inputs
can be connected per channel) can be connected per channel)
Current inputs 1 A / 5 A (IL1, IL2, IL3, Io) 1 A / 5 A (IL1, IL2, IL3, Io)
Binary inputs 24 V d.c., 3 mA (BI1, BI2) 24 V d.c., 3 mA (BI1, BI2)
Tripping relay Up to 250 V a.c./d.c. 5 A (T1, T2, T3, T4) Up to 250 V a.c./d.c. 5 A (T1, T2, T3, T4)
High-speed outputs Up to 250 V a.c./d.c. 2 A (HS01, HS02) Up to 250 V a.c./d.c. 2 A (HS01, HS02)
Quenching device outputs Optical fibre cable (at least 43 mA) (2x TX) Optical fibre cable (at least 43 mA) (2x TX)
Binary output 24 V d.c 20 mA (B01) 24 V d.c. 20 mA (B01)
Operating temperature (TU) –35 °C ... +70 °C –35 °C ... +70 °C
Tripping time of the relay 7 ms 7 ms
Tripping time HSO < 2 ms < 2 ms
Tripping time TX < 2 ms < 2 ms
Arc fault quenching time < 2-3 ms with DSRT QD / < 3-4 ms with DSRT QD II < 2-3 ms with DSRT QD / < 3-4 ms with DSRT QD II
Approvals VdS VdS
Detection Device (Point Sensor)
782 040 DSRT DD PS BACA
782 041 DSRT DD PS AACA
DSRT DD PS .... detection device for light detection (DSRT PS point sensors) including output for directly connecting two DSRT QD / DSRT QD
782 040 4013364245822 05 02 10 02 784 g
0,00 € II quenching devices.
782 041 4013364245839 05 02 10 02 784 g
0,00 €
Type DSRT ... DD PS BACA DD PS AACA
Part No. 782 040 782 041
Min. / max. voltage (UN) 18-72 V d.c. 92-265 V AC / DC
IP 50
Degree of protection (front side)
IP 50
Active Arc Fault Protection Degree of protection (rear side) IP 20 IP 20
177 x 52 mm
Dimensions of the front plate (H x W)
177 x 52 mm
157 x 45 x 164 mm
157 x 45 x 164 mm
Mounting dimensions (H x W x D)
S1, S2, S3, S4 (3 sensors (DSRT PS)
S1, S2, S3, S4 (3 sensors (DSRT PS)
Sensor inputs
can be connected per channel)
can be connected per channel)
Binary inputs
Up to 250 V a.c./d.c. 5 A (T1, T2, T3, T4)
Tripping relay 24 V d.c., 3 mA (BI1, BI2) 24 V d.c., 3 mA (BI1, BI2)
Up to 250 V a.c./d.c. 5 A (T1, T2, T3, T4)
Quenching device outputs Optical fibre cable (at least 43 mA) (2x TX) Optical fibre cable (at least 43 mA) (2x TX)
Binary output 24 V d.c. 20 mA (B01) 24 V d.c. 20 mA (B01)
Operating temperature (TU) –35 °C ... +70 °C –35 °C ... +70 °C
Tripping time of the relay 7 ms 7 ms
Tripping time TX < 2 ms < 2 ms
Arc fault quenching time < 2-3 ms with DSRT QD / < 3-4 ms with DSRT QD II < 2-3 ms with DSRT QD / < 3-4 ms with DSRT QD II
Approvals VdS VdS
Detection Device (Fibre Optic Sensor)
782 050 DSRT DD FS BAAA
782 051 DSRT DD FS AAAA
DSRT DD FS .... detection device for light detection (DSRT FS fibre optic sensor).
782 050 4013364245846 05 02 10 02 851 g
0,00 €
782 051 4013364245853 05 02 10 02 851 g
0,00 €
Type DSRT ... DD FS BAAA DD FS AAAA
Part No. 782 050 782 051
Min. / max. voltage (UN) 18-72 V d.c. 92-265 V AC / DC
Degree of protection (front side) IP 50 IP 50
Degree of protection (rear side) IP 20 IP 20
Dimensions of the front plate (H x W) 177 x 52 mm 177 x 52 mm
Mounting dimensions (H x W x D) 157 x 45 x 164 mm 157 x 45 x 164 mm
S1, S2, S3 (one fibre optic sensor (DSRT FS) S1, S2, S3 (fibre optic sensor (DSRT FS)
Sensor inputs
can be connected per channel) can be connected per channel)
Binary inputs 24 V d.c., 3 mA (BI1, BI2) 24 V d.c., 3 mA (BI1, BI2)
Tripping relay Up to 250 V a.c./d.c. 5 A (T1, T2, T3, T4) Up to 250 V a.c./d.c. 5 A (T1, T2, T3, T4)
Binary output 24 V d.c. 20 mA (B01) 24 V d.c. 20 mA (B01)
Operating temperature (TU) –35 °C ... +70 °C –35 °C ... +70 °C
Tripping time of the relay 7 ms 7 ms
Arc fault quenching time < 2-3 ms with DSRT QD / < 3-4 ms with DSRT QD II < 2-3 ms with DSRT QD / < 3-4 ms with DSRT QD II
Approvals VdS VdS
136 You will find detailed product information on our website Valid as of January 1, 2019