Page 9 - dehn-surge-protection-PV
P. 9

1 d.c. side (pv modules / inverter)

               Building without external lightning protection
               If a PV system is retrofitted and no external lightning
               protection system is installed, the solution according to
               the supplement 5 of the german version of the IEC/EN
               62305-3 can be used. It recommends to install a type
               2 surge protective device on the d.c. and a.c. side to
               protect the PV system.





                                            5


                              GJB
                              GJB
                       PC PC       =  ~  6 mm² Cu
                                       6 mm² Cu
                               4
                                                               DEHNguard  M YPV SCI
                                                                         ®
                      M M
                                                               type 2 arrester
                   SEB
                               MEB
                                                               Multipole, modular surge arrester for PV
                                                               systems: The patented SCI technology
                                                               prevents fire damage caused by d.c.
               Building with external lightning protection and   switching arcs
               sufficient separation distance
               The PV modules must be located in the protection   Type                 Part No.  U
               zone of the isolated air-termination system and the                              C
               separation distance must be maintained.          DG M YPV SCI 600 FM*   952 516  600 V
                                                                DG M YPV SCI 1000 FM*  952 515  1000 V
                                                  6             DG M YPV SCI 1200 FM*  952 517  1200 V
                separation distance s
                   OK
                     _ > s
                                           5


                              GJB
                              GJB
                       PC PC       =  ~  6 mm² Cu
                                       6 mm² Cu
                               4
                      M M
                   SEB
                               MEB



               Building with external lightning protection
               and insufficient separation distance
               If the separation distance cannot be maintained,
               for example in case of a metal roof, lightning   DEHNlimit PV 1000 V2 FM type 1 combined
               equipotential bonding must be implemented.      lightning current and surge arrester
                                                               Multipole spark-gap-based
                                                  6
                                                               combined lightning current
                                                               and surge arrester capable of
                separation distance s
                not OK                                         carrying lightning currents for
                    < s                                        PV generator circuits with wave
                                              5
                                                               breaker function
                                                                Type                   Part No.
                              GJB
                              GJB
                                       16 mm²
                       PC PC       =   16 mm²                                          900 345
                                       Cu
                                       Cu                       DLM PV 1000 V2 FM*
                                   ~
                               4
                      M M
                   SEB
                               MEB


    8