Page 13 - ferraz MV DIN fuse range
P. 13

®
         Limitor -G General Purpose fuse-links
         according to IEC 60282-1







         Selection table

          Rated voltage range                                         Transformer output [kVA]
           of fuse-link [kV]  Mode of protection
           Service voltage of   Rated current of fuse-link [A]  rel. short-circuit voltage          U  = 4%  U  = 5%
                                                                                                        K
                                                                               K
           transformer [kV]                 50    100   125  160   200   250  315   400   500  630   800   1000
                        Transformer rated current [A]  2,9  5,8  7,2  9,2  11,5  14,4  18,2  23,1  28,9  36,4  46,2  57,7
               6/12
                        Rated current of fuse-link [A]   6,3  6,3-10  10  16  16  16-25  25  25-40  40  40-50  50  50
               10
                        Transformer rated current [A]  1,5  2,9  3,6  4,6  5,8  7,2  9,1  11,5  14,4  18,2  23,1  28,9
              10/24
                        Rated current of fuse-link [A]  -  4  4-6,3  6,3  6,3-10  10  16  16  16  25  25   25
               20
         Table 5










          Catalog      Reference   Range          Un     In   L   D    I   1  R   P (W)  I²t   Weight
          Number       Number                     (kV)   (A)  (mm)  (mm)  (kA)  (mΩ)  @ In  (kA²s)  (kg)
          45DG120V6,3P  W1000151  General Purpose, striker  6/12  6,3  292  65  40  128  6  2  2,3
          45DG120V10P  X1000152  General Purpose, striker  6/12  10  292  65  40  70  8  3,8  2,3
          45DG120V16P  Y1000153  General Purpose, striker  6/12  16  292  65  40  35  10  14  2,3
          45DG120V25P  Z1000154  General Purpose, striker  6/12  25  292  65  40  20,5  15  36  2,3
          45DG120V40P  A1000155  General Purpose, striker  6/12  40  292  78  40  12,2  24  110  3,1
          45DG120V50P  B1000156  General Purpose, striker  6/12  50  292  88  40  9,9  31  150  3,7
          45DG240V4P  C1000157  General Purpose, striker  10/24  4  442  78  40  280  5  1,8  4,1
          45DG240V6,3P  D1000158  General Purpose, striker  10/24  6,3  442  78  40  256  11  2  4,1
          45DG240V10P  E1000159  General Purpose, striker  10/24  10  442  78  40  135  15  3,6  4,1
          45DG240V16P  F1000160  General Purpose, striker  10/24  16  442  78  40  70,3  21  14  4,1
          45DG240V25P  G1000161  General Purpose, striker  10/24  25  442  88  40  41,2  31  39  4,5



         Time-current characterictics
























          Fig. 13                                Fig.14
          6/12 kV                                10/24 kV







                                                                                                                  13