Page 2 - Ferraz semiconductor BS88
P. 2

Semiconductor fuses
                                                   Semiconductor (AC) fuses


                                                                                                      ®
                                                                            Other Protistor Fuses
                                                                     DIN Bracket Ferrule Fuses
                                                                    17x49 gRB/URB - 690 VAC






                                                         EXTREMELY HIGH BREAKING CAPACITY FUSES:
                                                         PROTECTION OF SEMICONDUCTORS
                                                         AS PER IEC STANDARD 60269.1 AND 4
                                                         690 V VOLTAGE RATING AS PER IEC 33

                                                         gR CLASS (CURRENT RATING 12 TO 90 A) AS PER
                                                          VDE 636-23
                                                         - CLEARING ALL OVERLOADS
                                                         - IMPROVED SAFETY AND PROTECTION
                                                         - ENABLING SELECTIVE COORDINATION WITH ALL FUSES
                                                           WITHIN DISTRIBUTION CIRCUIT

                                                         aR CLASS (CURRENT RATING 100 A) ACCORDING TO VDE
                                                         636-23 AND IEC 60269.4
                                                           CONNECTION AS PER:
                                                         -  GERMAN STANDARD DIN 43653/00C
                                                         -  BRITISH STANDARD BS 88-4

                                                         These fuses are UL Recognized






             Main Characteristics


             Voltage            Current  pre-arcing  Total clearing
              rating   Class    rating   2          2               Watts loss          Tested         Estimated
                                                    I t @ U
                                                         N
              U ( V )           I ( A )  I t @ 1 ms  I tt (A s)  0.8 I N    I N    Breaking capacity  Breaking capacity
               N
                                N
                                          2
                                                         2
                                                    2
                                         I tp (A2s)
                                 12         4.2       30        1.95        3.5
                                 16         9.6       65         2.2        4.0
                                 20        17.1       110        3.0        5.5
                                 25        26.8       170        4.4        8.0
                                 32        52.5       330        5.0        9.0
               690     gRB       35         69        430        5.2        9.5        200 k A          300 k A
                                 40         96        610        5.8       10.5        @ 690 V         @ 690 V
                                 45        130        820        6.3       11.5
                                 50        154        970        7.2        13
                                 55        210       1320        7.4       13.5
                                 63        310       1950        8.0       14.5
                                 75        520       3250        8.8        16
                                 80        620       3900        9.4        17
                                 90        840       5300        11         20
               690     URB       100       965       6150        13        23.5        200 k A          300 k A
                                                                                       @ 690 V         @ 690 V

             Minimum operating voltage for separate trip-indicator: 20 V














                                                          SCAC198                                              12/04
   1   2   3   4   5   6   7