                                                                                            BS88-4 Fuses
                                                              000 BS88 - 500 V to 690 VAC






                                             EXTREMELY HIGH BREAKING CAPACITY FUSES: PROTECTION OF POWER
                                             SEMICONDUCTORS AS PER IEC STANDARD 60269.1 AND 4, AND EN
                                             60269-1 AND 4

                                             500- 690 V VOLTAGE RATING (RATING 20 TO 400 A)

                                             gR CLASS (gRB RATINGS 20 TO 125 A) ACCORDING
                                             TO VDE 636-23
                                             - CLEARING ALL OVERLOADS
                                             - IMPROVED SAFETY AND PROTECTION
                                             - ENABLING SELECTIVE COORDINATION WITH ALL FUSES
                                             aR CLASS (URB RATINGS 75 TO 400 A) ACCORDING TO VDE 636-23
                                             AND IEC 269.4

                                             TWO MODELS ACCORDING TO BS 88-4 AND EN 60 269 .4
                                             STANDARDS; Z3 DRAWING (74 mm BETWEEN AXES) WITHOUT
                                             BLOWN FUSE
                                             INDICATION - WITH SEPARATE TRIP INDICATOR

                                             These fuses are UL Recognized




             Main Characteristics


             Voltage          Current   Pre-arcing
              rating  Class   rating    I 2 t @ 1 ms  Total clearing   Watts loss        Tested       Estimated
             U ( V )          I ( A )   I 2 t (A 2 s)  I 2 t (A 2 s)  0.8 I N   I N     Breaking   Breaking capacity
                              N
               N
                                          p
                                                                                        capacity
                               20          12      80 @ 660 V        3.8        7
                               25          20      150 @ 660 V       5.0        9
                               32          39      270 @ 660 V       5.5        10
              690 V   gRB                                                                200k A        300k A
                               40          70      460 @ 660 V       6.6        12
                               50         102      730 @ 660 V       7.7        14      @ 690 V       @ 690 V
                               63         210      1500 @ 660 V      8.8        16
                               80         475      2900 @ 660 V      9.9        18
                               100        970      6000 @ 660 V      11         20
                               125        1900     11800 @ 660 V    11.6        21
                               75         350      2250 @ 660 V     11.2       20.5
                               80         390      2500 @ 660 V     11.6        21
                               100        690      4200 @ 660 V     12.7        23
                               110        950      6800 @ 660 V     13.5       24.5      200k A
              690 V   URB      125        1300     8900 @ 660 V     14.3        26      @ 690 V        300k A
                               160        2700     16000 @ 660 V    17.0        31                    @ 690 V
                               200        5250     31500 @ 660 V    19.8        36
                               250        9900     52000 @ 660 V    24.8        45
                               315       15500     82000 @ 660 V    31.9        58
                               350       22400     110000 @ 500 V   31.9        58       120k A
              500 V   URB      400       33200     160000 @ 500 V   36.3        66      @ 500 V