Page 29 - Ferraz semiconductor BS88
P. 29

Semiconductor fuses
       Semiconductor (AC) fuses


       Other Protistor Fuses
                                 ®
       BS88-4 Fuses
       000, 2.000 BS88Z - 690 VAC






       DC Application data
              L/R (ms)                             Um (V)                         Rated    Curve  Ipm (A)
                                                                                 current
          100                                                                       50       a      150
                 c  b  a
                                              1400                                  65       a      200
           90                                            L/R =80 ms
                                                                                    75       a      270
                                                             L/R =25 ms
           80                                 1200                                  85       a      350
                                                                                    90       a      370
           70                                                  L/R =10 ms
                                              1000                                 110       a      500
           60                                                                      150       a      700
                                               800                                 180       b      1200
           50
                                                                                   200       c      1800
           40                                  600                                 250       c      2200
                                                                                   280       c      2200
           30
                                               400
           20                                                                      175       a      740
                                               200                                 200       a      870
           10
                                                                                   235       a      1000
            0                                    0                                 300       a      1400
                100  200  300  400  500  600  700    100  200  300  400  500  600  700  U (V)  355  b  2400
              0                       U (V)       0                                325       b      1900
        Above: Curves indicate permissible value of time cons-  Above: Curves indicate peak arc voltage  400  c  3600
        tant L/R as a function of DC working voltage.  Um which may appear across fuse termi-  450  c  4400
        Curve a:  Ratings from 175 to 300 A      nals at working voltage U.        500       c      4400
        Curve b: Rating 325 A                                                  Ipm values give minimum
        Curve c: Ratings from 355 to 500 A
                                                                               DC interrupting current in amps.
       Current limitation curves
                   Below: Curves indicate, for each rating value of peak let-through current  Ic as a function of available fault
            I (A)  current Ip.                                                                      Ip (A)
             C
        10 5                              (T000)            Ic =    2  Ip  (T: 2000)        Ic =    2  Ip
                                                                          URC
                      Ic = 2.5  Ip  gRB    URD      Ic = 2.5  Ip   250-280A  URD   Ic = 2.5  Ip    500 A
                                           URC
                                                                                                   400-450 A
                                                                                                   355 A
                                                                   200 A
                                                                                                   300 A
                                                                   150 A
                                                                                                   235 A
        10 4              Ic =    2  Ip                            180 A                           325 A
                                                                   110 A
                                                                                                   200 A
                                                                   85 A
                                    65 A                           90 A                            175 A
                                                                   75 A
                                    50 A
         3
        10
         2
        10
           2      3       4      5       6 2      3       4      5      6 2      3       4      5      6
          10     10      10     10     10 10    10      10     10     1010      10     10     10      10
        Time vs current characteristics
          t (s)       65  85  110  150 180  250-280  gRB-URC (000)  t (s)  175 200  235 300  325 355  400-450  URC (2000)
                     50  75  90  200  URD (000)                        500         URD (2000)
         10  4                                         10 4
                                       gRB
                                     a=130                                        a= 130
         10  3                       A2=0.6            10 3                       A2=0.67
                                     B1=1.25                                      B1= 1.25
                                                                                  B2= 0.67
                                     B2=0.6                                                Left: Curves indicate,
         10  2                       Cf3=0.8           10 2                       Cf3= 0.8  for each rated current,
                                                                                           pre-arcing time vs.
                                     URC-URD                                               R.M.S. pre-arcing cur-
           10                        a=130              10                                 rent
                                     A2=0.67
                                     B1=1.25
            1                                            1
                                     B2=0.67
                                     Cf3=0.85
         10  -1                                        10 -1
         10  -2                                        10 -2                                Tolerance for mean
                                                                                            pre-arcing current ±
                                                                                            8%.
         10  -3                                        10 -3
         10  -4                                        10 -4
            10        10 2     10 3       10 4 I (A)       10 2      10 3     10 4       10 5  I (A)
                                                          SCAC221
       12/04
   24   25   26   27   28   29   30   31   32   33   34