Page 39 - Ferraz semiconductor BS88
P. 39

Semiconductor fuses
       Semiconductor (AC) fuses


                                 ®
       Other Protistor Fuses
       BS88-4 Fuses
       17x49 gRB/URB - 690 VAC






       DC Application data                                                       Microswitch


            L/R (ms)
       100
        90                                          Um (V)
                                                                                             8.5
        80
        70                                     1100                                                   20
        60                                     1000
                                                                                               31     7
        50                                      900
                               2                                                                      10
        40                                      800
                                                                                              23   cosses à souder
        30                                      700                                                ou clips 2.8
        20                1                     600                               Designation Ref. Num. Weight Pack.
        10                                      500                                MC 6,3 GR 2.5  Y 310015   10 g 3 pieces
         0                                        0
           0                                        0                      U (V)
               100  200  300  400  500  600            100  200  300  400  500  600  Electrical characteristics:
                                   U (V)
                                                                                  I = 3 A - U = 250 VAC
                                                                                   N
                                                                                          N
        Above: Curves indicate permissible value of time  Curve indicates peak arc voltage  I = 2 A - U = 30 VDC
                                                                                   N
                                                                                          N
        constant L/R as a function of DC working voltage.
                                                     Um which may appear across the
        Curve 1: Ip ≥ 1,6 IN only for fuses gRB      fuse terminals at working voltage U.  Certain minimum operating vol-
        (current rating from 12 to 50 A)                                                   tage/current
        Curve 2: Ip ≥ 8 IN for fuses gRB et URB                                           20 V-100 mA
        NEW gR-CLASS
        OPTIMAL PROTECTION OF POWER EQUIPMENT               t              t
                                                              C   100A "aR"      100A "gR"
        Thanks to recent technological developments, Ferraz Shawmut today
                                                                         2h
        markets gR-class PROTISTOR ® fuses capable of clearing all types of over-
        loads, from low multiples of current ratings up to very high short-circuit  30s  C'   Example:
        currents. Enhanced performance enables these fuses to provide solu-               100A aR vs. 100A gR
        tions to many previously unsolved problems in power electronics: pro-
        tection of cables without the use of additional components,  protection
        of equipment from fire hazards, selective coordination of different fuses
        within a single power distribution installation...             I             I
                                                                300A        110A
                                                             minimum interrupting
                                                                current
                                                       SELECTIVE COORDINATION
                                                       gR-class semiconductor fuses can be utilized in association with gI and gG-class
                                                       low voltage power distribution fuses of the same current rating, installed upst-
                        aR             gR              ream. In a “selectively coordinated“ distribution installation, melting is limited
                                                       to the fuse associated with the faulted circuit, while upstream fuses remain
                                                       intact. This prevents unnecessary down-time due to power blackouts in non-
                                                       faulted branches.
                   Relay

                                                                                     gG 100A
                                                               Example of
                                                                selective
                                                               coordination    gR 100A  gR 100A
                   Before          After


                                                                             M           M
        aR-CLASS vs. gR-CLASS            FERRAZ SHAWMUT EXPERTISE
        aR-class fuses feature a high minimum inter-  gR-class fuses should be used in the design of low voltage equipment and in the protection of
        rupting current as compared with their cur-  power electronics equipment. Designers can often substitute a gR-class fuse for an aR-class fuse
        rent rating. The primary time-current charac-  (10x38, 14x51, 22x58, PSC 000 and 17x49 DIN80 or BS 88-4) but the reverse is not true:  an aR
        teristic of aR-class fuses is the CC’ curve,  fuse can never replace a gR fuse. Start protecting your new equipment with gR-class fuses today.
        above which another protection device must  The application  of gR class fuses, with current ratings less than 100 Amps,  offers enhanced pro-
        be associated. The gR-class fuse represents  tection, safety and reliability, along with reduced risk of replacement errors and assembly costs.
        considerably improved performance in semi-
        conductor protection.