KV Small-type distribution boards
                                 Technical details




       Operating and ambient conditions          KV Small-type distribution boards       Cable entry systems
   Service                                     KV Small-type    Empty boxes      ESM ...,         AVS 16

                                               distribution
                                               boards                            EVS 16
                            Application area   IP 54/65 design:
                                               Suitable for indoor installation - normal environment and/or protected outdoor -
                                               Resistant to occasional cleaning procedures (direct jet)
   DK                                          max. with high-pressure cleaner without additives
                                               water pressure: max. 65 bar, water temperature: max. 50° C, distance ≥ 0.5 m
                                               box and cable entries at least IP 65
                        Ambient temperature
                   - Average value over 24 hours  + 35° C       –                + 35° C          + 55° C
                             - Maximum value   + 40° C          + 60° C          + 40° C          + 70° C
                              - Minimum value  − 25° C          − 40° C          − 25° C          − 40° C
   KV                       Relative humidity    50% at 40° C   —                —                —
                                 - short-time  100% at 25° C    —                —                —
                              Fire protection  Demands
                     in the case of internal faults  placed on electrical devices from standards and laws
                                               governing operational equipment
                                               Minimum requirements
                                               - Glow wire test in accordance with IEC 60 695-2-11:
                                               - 650° C for boxes and cable glands
                                               - 850° C for parts of insulating material necessary to retain
                                                             current carrying parts in position
                           Burning behaviour
                 - Glow wire test IEC 60 695-2-11  750° C       750° C           750° C           750° C
                              - UL Subject 94  V-2              V-2              −                V-2
                                               flame-retardant  flame-retardant  flame-retardant   flame-retardant
                                               self-extinguishing  self-extinguishing  self-extinguishing  self-extinguishing
                         Degree of protection
                      against mechanical load  IK08 (5 Joule)   IK08 (5 Joule)   –                –
                             Toxic behaviour   halogen-free                      halogen-free     halogen-free
                                               silicone-free                     silicone-free    silicone-free
                                              “Halogen-free” in accordance with IEC 754-2 “Common test methods for cables - Determination of
                                              the amount of halogen acid gas”.
                                              To material properties see technical data.