Page 22 - MINISTACK Fuse Switch Disconnector Unit
P. 22

Operating & Maintenance





         Operation                           Maintenance                        Suggested Specification
         The following information details the  It is recommended that a six monthly     All fuse switch stacks are to be rated
         correct operating procedure for the  inspection and test be made using the  at either 50kA or 63kA and conform
         standard equipment supplied on a    following procedures:                 to the requirements of AS3439.1.
         Ministack assembly.                                                       Fuse switch disconnector units shall
                                             Note: If the equipment is operating
                                             in a dusty or corrosive atmosphere,   be rated at 660V AC and 250V DC.
         Fuse Switches
                                             this inspection should be made more     All fuse switch stacks shall be
         (a) Withdraw the sliding operating  frequently and appropriate remedial   provided with an integral fully
            handle.                          action taken.                         shrouded riser busbar system,
         (b) Move the handle upwards to the                                        encapsulated within the DMC
            ‘ON’ position or downwards to    Fuse Switches                         moulding of the fuse switch
            the ‘OFF’ position. Operate the  (a) Turn switch off.                  disconnector units. The line side
            switch handle firmly to its full limit.                                connection from the switch to the
                                             (b) Remove moving carrier from switch.
                                                                                   riser busbar system, shall be of a
         Carrier Removal/Fuse Replacement    (c) Visually check carrier contact blades  plug in type.
                                               for discolouration and arcing
                                                                                   All combination fuse switch units
                                               damage, replace if excessive.
                                                                                   shall be fitted with ASTA20 certified
                                             (d) Clean switch blades if necessary  LV HRC fuse links.
                                               and regrease.
                                                                                   Fuse switch stacks are to be
                                             (e) Ensure all fuse connections are   ALSTOM Ministacks or equivalents.
                                               tight to following torque values :  The fitted fuse links are to be GEC,
                                               1/200A      – 8-11 Nm               EE or GE Red Spot or equivalents.
                                               4/630/800A – 12-15 Nm               All future fuse switch disconnector
                                                                                   spaces shall be supplied to allow
                                                                                   fitting of future switch units at a later
                                                                                   date without supply interruptions.












                                             Note: The application of grease should
         To remove the fuse carrier, open    only be made on the lead-in chamfer
         the front door, withdraw operating  of the blades. The amount used should
         handle and apply sufficient upward  not be excessive. Shell LGP1 or Darina
         pressure to the operating handle    R2 grease must be used. DO NOT
         to release the interlock while at the  use vaseline or petroleum jelly.
         same time pulling the fuse carrier  Transport
         outwards in a horizontal direction.
         DO NOT depress the door safety      Switch must be transported in
         interlock during this operation.    ‘ON’ position.


                                                              22