Page 3 - MINISTACK Fuse Switch Disconnector Unit
P. 3

Ministacks





         ALSTOM Industrial Products Division  The fuse switch disconnectors are
         is continually developing the Ministack  defined as follows:
         range of switches to provide for the
         requirements of consulting engineers,  CMS
         contractors and switchboard builders.  Standard types which have been
         The latest range of Ministacks include:  tested with the arc being initiated
                                             on the load side terminals.
            Uprated busbar (910A) for 100A
           & 200A stacks, 2 to 10 high.      CMSE
            New style sandwiched copper      Special types tested where the arc
           cable connectors fitted to the rear  was initiated within the fuse switch
           moulding of 100A & 200A units.    disconnectors and substantial 3-phase

            3&4 high 400A & 630A Ministacks.  arcing currents were not interrupted    CMS
                                             by the fuse links for the full duration
            NEW  comprehensive range of
                                             of test time nominated.
           mixed stacks.
         The Ministack now offers industry a  Service Requirements and
         clear choice in low voltage switchboard  Temperature Rise Guidelines
         design. This design suits Form 1 to  (CL.6.1.1) – AS3947.1
         Form 4 types of separation. With the  Under normal service conditions as
         addition of optional terminal shrouds  defined in AS3947-1 (i.e. “The ambient
         plus the necessary barriers provided  air temperature does not exceed
         by the switchboard builder, Form 4  +40°C and its average over a period
         separation is achievable.
                                             of 24 hrs does not exceed +35°C”),
         Fuse switch disconnector units are  individual switch units in a stack are
         available which have been successfully  fully rated.  Derating is however
         tested, and meet the requirements of  necessary when switch ratings exceed
         the standard test as indicated by   the assigned main busbar rating.         CMSE
         Clause EE3 in Appendix EE of AS3439.1  Load diversity to be taken into account.
         or special test as specified in Clause
         EE6 of Appendix EE.                 For reliable operation, regular main-
                                             tenance is required. Refer page 22.

         Range:
                                                                            Main Busbar Incomer Direction
         Switch Rating Amps  Outgoing Terminal Connection Types  Height of Stack  Above  Below  Above & Below  Busbar Rating Amps
         100 & 200     Front Connected – Right Hand  2-10H      Above     Below    Above & Below    910
                       Front Connected – Left Hand
                       Back Connected
         400 & 630     Front Connected – Right Hand  2-4H       Above     Below    Above & Below    1000
                       Front Connected – Left Hand
                       Back Connected
         800           Front Connected – Right Hand  1&2H       Above     Below    Above & Below    1000
                       Front Connected – Left Hand
                       Back Connected
         Mixed Stacks  Front Connected – Right Hand  See page 4  Above    Below    Above or Below   1000/910
                       Front Connected – Left Hand
                       Back Connected


                                                              3
   1   2   3   4   5   6   7   8