Page 16 - photovoltaic-2019-V19
P. 16

SURGE PROTECTION - DC






       LIGHTNING & SURGE PROTECTION TYPE I & II
       Features:
       - High discharge.
       - Lightning protection.
       - Remote monitoring.

          Device                      In 8/20μs         Total      Voltage
         Type Acc.     System     Nominal Discharge   Discharge   Protection         Part No.
         IEC 61643     Voltage      DC+/DC- => PE      Current     level Up
       Lightning Current and Surge Arrestors
          T1 & T2      600VDC           15kA       12.5kA 10/350μs  1.75kV      DCBYPVSCI600*
          T1 & T2      1000VDC          15kA       12.5kA 10/350μs  2.5kV      DCBYPVSCI1000*
          T1 & T2      1500VDC          15kA       12.5kA 10/350μs  3.75kV     DCBYPVSCI1500*

                                                                                                     DCBYPVSCI




       SURGE PROTECTION TYPE II


       Features:
       - High discharge.
       - Replaceable Cartridges.
       - Remote monitoring.

          Device                      In 8/20μs        Total       Voltage
         Type Acc.     System     Nominal Discharge   Discharge   Protection         Part No.
         IEC 61643     Voltage      DC+/DC- => PE     Current      level Up
        Modular Surge Arrestors
            T2         150VDC           10kA         20kA 8/20μs   ≤0.8kV     DGMYPVSCI150FM
            T2         600VDC          12.5kA        40kA 8/20μs   ≤2.5kV     DGMYPVSCI600FM
            T2         1000VDC         12.5kA        25kA 8/20μs    ≤4kV     DGMYPVSCI1000FM
            T2         1200VDC         12.5kA        25kA 8/20μs   ≤4.5kV    DGMYPVSCI1200FM
            T2         1500VDC         12.5kA        25kA 8/20μs    ≤6kV     DGMEYPVSCI1500FM        DGMYPVSCI






       SURGE PROTECTION TYPE II (MONOBLOCK)
       Features:
       - Monoblock.
       - High discharge.

          Device                      In 8/20μs        Total       Voltage
         Type Acc.     System     Nominal Discharge   Discharge   Protection         Part No.
         IEC 61643     Voltage      DC+/DC- => PE     Current      level Up
        Monoblock Surge Arrestors
            T2         600VDC          12.5kA        40kA 8/20μs   ≤2.5kV        DGYPVSCI600*
            T2         1000VDC         12.5kA        40kA 8/20μs    ≤4kV        DGYPVSCI1000*
                                                                                                     DGYPVSCI
       * Add FM to end of part number for signal contact.











    17  Photovoltaic Catalogue v-19                    www.ipd.com.au                            Phone: 1300 556 601