TECHNICAL DATA









          Features                               Description

          General Data
          Standards                              AS/NZS 61439-1 & 2 : 2016
                                                 Low voltage power switchgear and control gear assemblies, power distribution boards,
          Applications
                                                 motor control centres, PLC & DCS panel boards
          Installation                           Outdoor
          Mounting Possibilities                 Floor Standing
          Plinth                                 3mm mild steel hot dip galvanized
          Internal Framework                     RAL 7032 Grey / RAL 2000 Orange
                                                 Door and Cover Frames: 2mm Marine grade aluminium 5052 H32*
          Cladding
                                                 Doors, Covers and Rainhoods: 3mm marine grade aluminium 5052 H32*

          Mechanical Data
          Field/Tier Arrangement                 Front/Back Connected
          Cable Entry                            Bottom
          Compartment Types                      Fixed
          Access                                 Front/Rear
          IP Rating                              IP56 (Outdoor)
          Form of Segregation                    1, 2a, 2b, 3a, 3b, 4a, 4b
                                                 Width  - 2400mm (Extendable)
          Maximum Dimensions of a Transport Section  Height - 2200mm (+ Plinth and Rainhood)
                                                 Depth  - 1000mm
          Electrical Data
          Rated Operational Voltage (U )         415V/690V/1000V
                              e
          Rated Insulation Voltage (U)           690V/1000V
                             i
          Rated Frequency (f)                    50Hz
          Rated Impulse Voltage (U  )            Up to 12kV
                           imp
          Rated Current (I )                     Up to 3200A, contact IPD for higher ratings
                     n
          Rated Short Time Current (I )          Up to 50kA 1 sec, contact IPD for higher ratings
                             cw
          Internal Arcing Fault Containment      AS/NZS 61439 - 1 & 2 : 2016 (Appendix ZD)
          Earthing Systems                       TN-C, TN-S, TN-C-S, TT, IT

























        46 |  EXT56-R01